E22-2 - ADS/SRV Flashcards

1
Q

When will drywell pressure be bypassed on ADS logic?

A

If Rx level is < -150.3” for more than 9.2 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the LO-LO set logic?

A

Durn Burn Durn Green Apple Farts

Initial Lo-Lo set Reset

  • 51D 1103 1033 926
  • 51B 1113 1073 936
  • 47D 1113 1113 946
  • 47G 1113 1113 946
  • 51A 1113 1113 946
  • 51F 1113 1113 946
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How is LO-LO set reset?

A

manually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What valves are ADS valves?

A

B21:

  • F041D
  • F041F
  • F041K
  • F047A
  • F047L
  • F051A
  • F051B
  • F051C

Dad Fought Kids And Lost, ABC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What valves can be operated from Remote Shutdown Panel?

A

Lo Lo set valves

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

When do SRV valves open for relief operation?

A

1 valve - 1103 psig open, 1003 close

10 valves - 1113 psig open, 1013 close

9 valves - 1123 psig open, 1023 close

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How many SRV’s per steam line?

A

A and D have 4 each

B and C have 6 each

20 total

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Purpose of the vacuum breakers?

A

Prevent vacuum from condensing steam in discharge piping, causing suppression pool to enter piping and eventually water hammer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When do valves open in safety mode?

A

8 valves @ 1165 psig

6 valves @ 1180 psig

6 valves @ 1190 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How many ADS valves can be operated from Remote Shutdown panel?

what valves are they?

A

2

(4 switches…. 2 switches on each panel)

51 A/B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

How much air pressure is supplied to ADS valves and SRVs?

A

ADS supplies 165 psig to ADS and F051D.

All other SRVs have Instrument air @ 120 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How many accumulators does each SRV have?

A

Non ADS except 51D have 1.

ADS and 51D have 2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How does light indication show a SRV open/close?

A

>= 30psig shows valve open (red) tailpipe pressure

< 30 psig shows valve green (closed) tailpipe pressure

valve can be opened, yet showing closed if tailpipe pressure is < 30 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

what powers logic to tailpipe pressure?

A

Div 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the purpose of ADS?

A

Serves as a backup to HPCS to depressurize the reactor so that Low Pressure ECCS can inject

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Purpose of SRV?

A

SRVs help to control Rx pressure < 1325 psig

17
Q

How many SRVs?

A

20

18
Q

How many SRVs are ADS valves?

A

8

19
Q

Where are the SRVs located?

A

main steam line, upstream of MSIV

20
Q

What two modes can SRVs operate in?

How does each mode work?

A

Safety mode - mechanical (Rx pressure vs Spring)

Relief mode - pneumatic

21
Q

Power supplies for the SRVs?

A

Div 1, 11DA

Div 2, 11DB

22
Q

what valves does ADS Air supply?

A

ADS valves AND F051D

23
Q

How many pilot soleniods must be energized to open SRV?

A

Normally de-energized, energizing ONE will allow SRV to open.

energize one to open

de-energize two to close

24
Q

When does the high temp alarm come in for the tailpipe temp?

A

155ºF

25
Q

What happens to ADS logic if an ECCS pump trips?

A

Logic resets

26
Q

When does the ADS low air receiver annunciator come in?

A

< 152 psig

27
Q

What sensors must energize to set off ADS?

A

Div 1 - A&E or Div 2 - B&F

28
Q

What is the logic after ADS receives a signal?

A

11.4” AND -150.3” AND 1.39# DW (DW can be bypassed if <150.3” for 9.2 minutes)

THEN, 105 second time delay

THEN ECCS discharge pressure (145# LPCS, 125# RHR A/B/C

29
Q

If AC power is lost, is the logic lost to ADS?

A

NO