What is the AUTO permissive for LPCI injection? (valve open permissive)
< 476 psig
what is the manual permissive for opening LPCI injection valve?
< 450 psig
What are the temperature limits for the suppression pool?
< 95 deg F without testing, >1%
<105 deg F if heat is being added to pool (RCIC) >1%
<110 deg F, < 1% Rx power
What 2 modes of RHR will AUTO initiate?
LPCI
CTMT spray
what order do the ECCS systems turn on?
- 5 sec, RHR C and LPCS
7. 5 seconds, RHR A/B
What is the CTMT spray logic for Div 1 and Div 2?
Must have LPCI signal for division first;
THEN,
Div 1 - (CTMT) A or C, AND, (DW) A or E
Div 2- (CTMT) B or D, AND, (DW) B or F
what is the max flow of a RHR pump?
7450 gpm @ 125 psid
what is the max flow for RHR jockey pump?
40 gpm @ 50 psig
What combination of signals will initiate LPCI for Div 1 and 2?
1 A and 1 E for Div 1
1 B and 1 F for Div 2
2 levels or 2 pressures will always do it
1 level and 1 pressure MAY do it under the right logic.
What are the ECCS Acceptance criterias?
CLOTH
- Core remains amenable to cooling
- Long term cooling
- Oxidation of cladding not to exceed 17% total cladding thickness
- Temp of fuel cladding not to exceed 2200 deg F
- Hydrogen generated from chemical reaction of the cladding with water or steam shall not exceed 1%.
what is the normal position of the F024 A/B and F021 (return to Supp Pool)
Normally closed and receives a closed signal on a LPCI signal
explain the 2 valve logic diagrams (since i can’t draw on this app)
F004 looks at the F006.
F006 looks at the F004 and F024.
F024 looks at the F004
F027 looks at the F028 and F042
What additional purpose does the RHR C Jockey pump have?
Reference leg fill for Div 2 suppression pool level
What happens to min/flow when starting up Shutdown Cooling?
Has 8 second time delay to prevent putting RX water in the suppression pool
What does RHR A/B Jockey pump do?
Feedwater leakage control system
How are valves aligned in Standby?
Aligned for auto initiation of LPCI or CTMT spray
What are the setpoints to initiate LPCI?
- 150.3” Rx Water level
1. 39 DW Pressure
What divisions does each RHR pump come from?
Div 1 - RHR A, LPCS
Div 2 - RHR B/C
What pressure must RX be at to inject RHR in LPCI mode?
476 psig
Where does water come from for CTMT Flooding?
SSW B downstream of RHR HX