DCS Flashcards

1
Q

On a 10% Manual runback, how much will the Target Load Lower by in U1?

A

114.9 MW @ 100 MW / min

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

On a 10% Manual runback, how much will the Target Load Lower by in U2?

A

121.7MW @ 100 MW / min

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

On a OP delta T and OT delta T Runback, What will the target load be?

A

30 MW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What power must we be at for the Loss of Feed Pump Runback to be enabled?

A

60% Power

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How does a Loss of Feedpump Runback respond in U1?

A

Goes to 625 MW @ 600 MW/min

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How does a Loss of Feedpump Runback respond in U2?

A

Goes to 90% at 1000 MW/min then to

60% @ 140 MW/min (until < 725 MW)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

If we get a Power Load Unbalance Runback, what will the Load Target be?

A

30 MW

and switch to MW OUT

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When is a power load unbalance runback armed?

A

1st stage pressure > 40%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Regarding MW Control, what does MW In mean?

A

Valves move to maintain MW

based on Circ Water, etc

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Regarding MW Control, what does MW Out mean?

A

Valves do not move

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the IOPs overspeed trip setpoint?

A

110%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the only trip input from the Turbine Supervisory (TSI)?

A

Thrust Bearing Wear

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Will a failure of all 3 speed sensors trip the turbine on the grid?

A

NO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What are the power supplies for IOPs?

A

CRID I, II and III

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the primary tripping device for the turbine?

A

Trip Block Assembly

2/3 solenoids de-energize

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What will force the MFP to Speed Control?

A

Both MS Press Xmitters Fail

Both MFP Hdr Press Xmitters Fail

MFP DP Setpoint Xmitter Fails

Other MFP Tripm when >60% Power

MFP Speed > 5220 (5300) rpm

17
Q

What is the purpose of DCS?

A

Supply hydraulic fluid for stop/control valve operation during normal and emergency conditions