A certificate issued by the department to an individual representing that such individual has completed all requirements for the master plumber or master fire suppression piping contractor license but has not obtained a seal or plate; and that such certificate has been renewed as required and is currently in effect. The ________________________________ shall bear the name of the holder and the certificate number. The holder of the _____________ is not a licensed master plumber or licensed master fire suppression piping contractor and may practice the trade for which the certificate is issued only under the direct and continuing supervision of a licensed master plumber or licensed master fire suppression piping contractor or, with respect to a city employee under the direct and continuing supervision of a supervising licensed master plumber or licensed master fire suppression piping contractor (Admin. code 2014 — 87, 28-401.3)
Certificate of competence
A standpipe to which a sprinkler system is connected or is being connected (Admin. code 2014 — 87, 28-401.3)
Combined standpipe system
(3)Responsible control exercised by a licensed individual, either personally or through one or more but no more than three, levels of competent supervision over individuals performing the actual work of the licensee’s trade who are (i) in the direct employ of an individual who is a licensee, or (ii) in the direct employ of a city agency employing the licensee or (iii) in the direct employ of a business employing the licensee, as allowed by the department, or (iv) where the licensee uses his or her license on behalf of the business, in direct employ of such business provided that such business is disclosed to the department pursuant to this chapter (Admin. Code 2014 — 87, 28-401.3)
Direct and continuing supervision
Same as question #3, such control shall be evidenced by such licensee’s ______, and ______ where applicable, upon any required statements, applications and/or permits and by demonstrating involvement of the license in the operations of the business, including hiring of employees, responsibility for financial matters, and oversight of work performance. (Admin. Code 2014 — 87, 28-401.3)
Signature, Seal
Direct and continuous supervision includes ____________ of such supervision and such other requirements as the commissioner may prescribe by rule for a particular license type (Adm.code 2014 — 87, 28 - 401.1)
Field inspection / Direct employ / Indirect employ
An individual is in the ______ of a licensee or business or city agency when such individual is on the payroll of such licensee or business or city agency and under the common law rules applicable in determining the employer-employee relationship has the status of an employee( Admin. code 2014 — 87, 28-401.3)
Direct employ
Direct employee SHALL NOT be evidenced by ( Admin. code 2014 — 87, 28-401.3)
Word of mouth, promises, lunches and friendships
The installation, maintenance, repair, modification, extension, or alteration or testing of a fire suppression piping system in any building in the city of New York ( Admin. code 2014 — 87, 28-401.3)
Fire suppression piping work
All applications for license or certificate of competence shall be at least 18 years of age, shall be able to read and write the english language, shall be of good moral character, shall be fit to perform work authorized by the particular license or certificate of competence and shall meet additional qualifications that may be prescribed for the particular license or certificate of competence. The department may refuse to qualify an applicant if it has found that the applicant ( Admin. code 2014 — 89, 28-401.3)
Violated any law, rule, or regulation of the department resulting in a suspension or revocation of a department issued license
Except as otherwise specified for the particular license type, applicants for a license shall be required to take an examination in accordance with the rules of the department. Every applicant shall commence the license application process with the department within _______ year of passing the examination for licensure and shall furnish the department a completed license application within _______ year of SUBMISSION of the first filing. Failure to provide all requested documents in a timely manner will constitute an incomplete application and will result in denial of the license ( Admin. code 2014 — 89, 28-401.3)
1,1
Every applicant for a license or certificate shall submit to investigation as directed by a government entity in order to determine the applicant;s ( Admin. code 2014 — 89, 28-401.8)
Character / Fitness
The applicant shall furnish the department with ( Admin. code 2014 — 89, 28-401.8)
Payment for the actual cost of conducting the background investigation
Failure of the applicant to provide the department all requested and completed documents or any other information necessary for completion of the investigation in a timely fashion ( Admin. code 2014 — 89, 28-401.8)
Will constitute a reason to move on to charge you with a felony
(14) Except as noted otherwise for a particular license, or exempted by the commissioner pursuant to rule, prior to the issuance of a license , or during the renewal thereof,the applicant shall file with the department satisfactory evidence of a commercial general liability insurance policy in the amount of ( Admin. code 2014 — 89, 28-401.9)
One-million dollars
Same as question #14 Such other amount as the commissioner may require together with satisfactory evidence of ( Admin. code 2014 — 89, 28-401.9)
Compliance with workers’ compensation law and the disability benefits law / Required insurance shall be maintained for the duration of the license / Any changes in coverage, insurance renewals, or policy status shall be provided to the department in accordance with the department rules
For licenses that require a plate and/or the application of a seal, the plate and/or seal shall be issued with the license except as provided otherwise in this chapter. The license, plate and the seal (Adm. Code 2016 — 89, 28-401.10)
Are the property of the department and are not transferable by the licensee / to licensee shall make or cause to be made duplicates of a department-issued license, plate or seal / The loss or theft of a license , plate or seal must be reported to the department within FIVE calendar days
All licenses issued by the commissioner for which an examination is required shall expire ______ years from the date issuance thereof, and may be renewed every ______ years thereafter without examination (adm, Code 2014 — 89, 28-401.11)
3,3
The commissioner shall have the authority to stagger the issuance of licenses for (Adm. code 2014 — 89, 28-401.11)
Three-year terms
All licenses NOT requiring examination shall expire ____ year from the date of issuance thereof, and may be renewed each year thereafter except as otherwise noted for a specific license (adm. code 2014 — 89, 28- 401.11)
One.
Applications for renewal of a license or certificate of competence shall be accompanied by the renewal fee and such additional information as the commissioner may require, and shall be made at least _______ calendar days but not more than _______ calendar days prior to the expiration date of same (Adm. code 2014 — 89, 28-401.12)
30,60
Applicants shall provide evidence satisfactory to the department that he or she is fit to perform the work authorized by the particular license as provided by department rule. Applications for renewal is subject to investigation by the department. The failure of an individual o renew his or her license or certificate of competence shall have (Adm. code 2014 — 89,90, 28-401.12)
The effect of cancellation of the license or certificate of the license or certificate of competence upon expiration, and the holder of a plate and/seal issued by the department shall be immediately surrender such plate and/or seal to the department. / A person who fails to renew a license or certificate if competence within the time period set forth in this section 28-401.12 may apply for later renewal or statement of such license pursuant to section 401.13. / The department may, following notice and an opportunity to be heard, refuse to renew license or a certificate of competence on any grounds on the basis of which it could dent suspend or revoke such license
If a license or certificate of competence expires, the individual may apply for late renewal of the license or certificate of competence, within _____ year of the date of its expiration without examination but subject to applicable late renewal fee. There after up to ________ years after the date of expiration, the commissioner may reinstate the license or certificate of competence without examination upon the applicant’s demonstration to the commissioner’s satisfaction of continued competence in the respective trade and satisfaction of any applicable continuing education requirements but subject to applicable late renewal fees (Adm. code 2014 — 90, 28-401.13)
One, five
Applicants for late renewal and reinstatement shall provide evidence satisfactory to the department that he or she is fit to perform the work authorized by the particular license as provided by department rule. A license or certificate of competence shall not be reinstated after_______ years from date of expiration (Adm. code 2014 — 90,28-401.13)
5
(24)The commissioner may promulgate rules to require applicants for renewal of licenses or certificate of competence to complete prescribed number of hours continuing education courses by the department within the term preceding the application for renewal and to provide proof of the same in a form acceptable to the department. Such proof, when required, shall be submitted with fee the application for renewal. The cost of the renewal fee for master plumber license (certificate of competence) (Adm. code 2014 — 90, 28-401.14, 91, 28-401.15 Schedule of fees)
$150 triennially
Same as question #24, the cost of the renewal fee for master fire suppression piping contractor (class A,B, or C) license certificate of competence (Adm. code 2014 — 90,28-401.14, 91, 28-401.15 Schedule of fees)
$150 triennially
Test 5.1 Question
Answer
The installation, maintenance, repair, modification, extension, or alteration or testing of a fire suppression piping system in any building in the city of New York ( Admin. code 2014 — 87, 28-401.3)
Fire suppression piping work
A standpipe to which a sprinkler system is connected to (Adm. code. 2014, 87, 28-401.3)
Combined standpipe system
An automatic valve is installed on the discharge side of a positive displacement pump to relieve pressure prior to the pump driver reaching operating speed (NFPA 20-2013 — 20-11, 3.3.57.1)
Dump valve
Of the following, which is considered, the least important pipe hanger support system installation
Type of pipe joint
Class 1 manual standpipes are allowed in the open parking garages where the highest floor is located not more than ______ feet above the lowest level of fire department vehicle (NYC bldg. code 2014 — Chapter 9, P214, 905.3.1 Ex. 2)
150
gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. Gauges not accurate within ________ percent of the full scale shall be calibrated or replaced (NFPA 25, 2-13 — 25-23, 6.3.4.1 & 2)
3%
Hydrostatic tests of not less than 200 psi pressure for two hours, or at 50 psi in excess of the maximum pressure, where maximum pressure is in excess of 150 psi, shall be conducted every _____ years on manual standpipe systems and semiautomatic dry standpipes, including piping the fire department connections (NFPA 25-2014, 25-23, 6.3.2.1*)
5
Where the design specifications require any part of the piping system to be welded in place, welding of sprinkler piping shall be permitted where the welding process is performed in accordance with ________, standard for fire prevention during welding, cutting, Other hot work (NFPA 13- 2007 — 13-30, .5.2.2.2)
NFPA 51B
Back rings are not permitted on welding pipe connections in most fire suppression piping systems because they will most probably
Reduce the inside diameter at the welded point
A valve has the number 300 cast on the side of the valve the number indicates
Pressure rating of the valve
Extra strong weight seamless steel pipe corresponds to
Sch. 80
Pump trouble; when stuffing box is too tight or packing improperly installed, worn, defective, or of incorrect type (NFPA 25, 2014 — 25-113, C.1.5)
Loosen gland swing bolts/ Remove stuffing box gland / Replace packing
The nominal pipe size of the pipe refers to the pipes
Inside diameter
A threaded fitting used to join two pipe sections of the same diameter is known as a
Coupling
Of the following the color of the fixed electrical equipment ground wire should be
Green
Of the following types of heat detectors the one that does not initiate an alarm when the detecting element reaches a predetermined set temperature is known as
Rate of rise detector
Of the following types of threading equipment the type of equipment the type of equipment that cuts a groove into the pipe is
Grooving machine
Piping materials are listed at $1000. If $15%, 10%, 8% discount is allowed the net purchase cost is most nearly
$704
Assume you have assigned 24 fitters to install a fire suppression piping system, that must be completed in 16-days, at the end of 12-days, only 2/3 of the job has been completed, in order to complete the job on time, you should assign a minimum of
12-extra fitters
The alarm apparatus for a wet pipe system shall consist of a listed (NFPA 13, 2007 — 13-32, 6.9.2.1)
Alarm check valve
The alarm apparatus for a dry pipe system shall consist of listed (NFPA 13, 2007 — 13-32, 6.9.2.2.1)
Alarm attachments to the dry pipe valve
When water pressure exceeds 175 psi (12.1 bar), valves shall be used in accordance with (NFPA 13, 2007 — 3-32, 6.7.1.1)
Their pressure ratings
The fire department connection(S) shall use an (NFPA 13, 2007 — 13-32, 6.8.1*)
NH internal threaded swivel fitting(S) with an NH standard thread(S) / Where at least one of the connections shall be the “2.5 - 7.5 NH standard thread “ / As specified in NFPA 1963, Standard for the Fire Hose connections
All control, drain, and test connection valves shall be provided with (NFPA 13, 2007 — 13-32, 6.7.4.1)
Permanently marked weatherproof metal identification signs / Permanently marked weather proof plastic identification signs
The alarm apparatus for deluge and preaction systems shall consist of alarms actuated ______ by the detection system and the flow of water (NFPA 13, 2007 — 13-32, 6.9.2.3)
Independently
The compressed air supply required for dry. pipe systems, shall be from a source (NFPA 13, 2007 — 13-34, 7.2.6.2.1)
Available at all times
Listed CPVC sprinkler pipe and fittings should be protected from freezing with (NFPA 13, 2007 —13-257, A.7.6.2)
Glycerine only
All permitted antifreeze solutions are _____ water (NFPA 13, 2007 — 13-257, A.7.6.3.1)
Heavier than
Sprinkler system discharge criteria for the protection of flammable and combustible liquids shall comply with (NFPA 2007, 13-191, 21.2.1)
NFPA 30
For trapeze hangers, all angles shall be installed with the (NFPA 13, 13-92, 9.1.1.6.3)
Equal sides / Longer leg vertical
Of the following types of wrenches the one which most nearly resembles a tool for installing or replacing a sprinkler head
Double open-end wrench
A spanner wrench is mainly used for
Couplings and uncoupling of caps for a siamese hose connection
The basic difference between a pre-action and a deluge sprinkler system (NFPA 13,2007 – 13-19, 3.4.9*)
Heat and smoke must be detected
A sprinkler that directs from 40% to 60% of the total water initially in a downward direction and that is designed to be installed with the deflector either upright or pendent (NFPA 13, 2007, 13-19, 3.6.2.5)
Old-style/conventional
Caps on a siamese connection, for standpipe systems are painted (NFPA 14, 2007 — S-26, 4.8.2.1Q)
Red
Standpipes and lateral piping supplied by standpipes shall be located: (NFPA 14, 2007 — S-39, 6.1.2.2Q)
In enclosed exit stairways
Of the following standpipe systems, the one that requires a pitot tube gauge reading test is the
Fire pump
Where required by NFPA, sample sprinklers shall be submitted to a recognized testing laboratory acceptable to the authority having jurisdiction for field service testing (NFPA 25, 2014 — 25-17, 5.3.3.3*, 5.3.1.1.1, 5.3.1.1.2)
Where sprinklers have been in service for 50-years, they shall be replaced or representative samples from one or more samples areas shall be tested / Test procedures shall be repeated at 10-year intervals / Sprinklers manufactured prior to 1920 shall be replaced
Sprinklers manufactured using fast-response elements that have been in service for 20-years shall be replaced or representative samples shall be tested and then retested at _________intervals (NFPA 25, 2014 — 25-17, 5.3.1.1.3*)
10-year
Sprinklers manufactured prior to ________ shall be replaced (NFPA 25, 2014 — 25-17, 5.3.1.1.1.2)
1920
Dry sprinklers that have been in service for 10-years shall be replaced or representative samples shall be tested and then retested at (NFPA 25,2014 — 25-17, 5.3.1.1.1.6*)
10-year intervals
Where sprinklers have been in service for 75-years, they shall be replaced or representative samples from one or more sample areas shall be submitted to a recognized testing laboratory acceptable to the authority having jurisdiction for field service testing and repeated at (NFPA 25, 2014 - 25 - 17, 5.3.1.2*)
5-year intervals
When a representative sample of sprinklers for testing is required a minimum of not less than_________ sprinklers or 1% of the number of sprinklers per individual sprinkler sample, whichever is greater (NFPA 25, 2014 - 25 - 17, 5.3.1.2*)
4
Where ________ sprinkler within a representative sample fails to meet the test requirement, ALL SPRINKLERS within the area represented by that sample shall be replaced (NFPA 25, 2014 — 25-18, 5.3.1.3)
1
Where addition or modification is made to an existing system affecting more than 20-sprinklers, the new portion shall be isolated and tested at not less than __________ for _________ (NFPA 13, 2007 — 13-225, 24.2.1.5)
200 psi, 2-hours
Modifications that cannot be isolated for testing purposes, such as relocated drops (NFPA 13, 2007 — 13-225, 24.2.1.6)
Shall not require testing in excess of system working pressure
Of the following examples, American Standard threaded designations, the one that applies to connections that connect to or with fire pump hoses
3-6 -NH
Assume you have assigned 12 fitters to install a fire suppression piping system that must be completed in 8-days. At the end of 6 days, only 2/3 if the job has been completed. In order to complete the job on time you should assign a minimum of
6-extra fitters
Activation of the initiating device shall occur within _________ of waterflow at the alarm-initiating device when flow occurs that is equal to or greater than that from a SINGLE SPRINKLER OF THE SMALLEST ORIFICE size installed in the system. The waterflow device should be field adjusted so that an alarm is initiated no more than ___________ after a sustained flow of at least 10-gpm (40 L/min). (NFPA 72,2010, 17.12.2*, 72-215, A.17.12.2)
90-Seconds
Test 5.2 Question
Answer
Fire department connections serving a non-automatic dry sprinkler system shall have the ENTIRE connection painted (NYC Fire code 2014 — 120, 912.4(3))
Silver
In a sprinkler system a check valve is installed vertically in the piping from the city water connection. Of the following types of check valves the one which should be used in the installation is a (NFPA 13, 2007 — 13-86, 8.16.1.1.3.4)
Spring loaded check valve
Blind flanges are installed in piping systems mainly to provide a means to
Gain easy access to the interior of a pipeline and/or fitting
Fire department connections shall be located at distance (NYC Fire Code 2014 — 120, 912.2.2)
From the nearest fire hydrant
According to the American Standard Pipe Thread System the number of threads per inch that properly threads a 2-inch pipe should have
11-1/2-threads per inch
Of the following types of valves, a valve that would allow you to check the sprinkler system flow would be
Test or drain valve
When an oxy-acetylene torch is used for making a brazed joint, the type of flame that should be avoided is
Oxidizing flame
The limiting length that determines whether a length of pipe is threaded on both ends is considered either as cut pipe or a nipple is
12-inch
Of the following, the one who is responsible for all welding installed in a fire suppression piping system is (NYC Admin. Code 2014 — 101, 28-410.1 (1))
The licensed master fire suppression piping contractor
Of the following types of copper tubing, the one that has the greatest wall thickness
Type “K”
In order for a synchronous motor to operate properly a motor must be supplied with
Both A.C. and D.C.
Of the following classifications of electric motors, a general purpose motor that would most likely be used where operating conditions are relatively clean and dry is the
Open drip-proof motor
Of the following types of filler metals for brazing the one which can produce HIGHLY TOXIC fumes when brazing is
BAG-2
A clear space shall be required around fire department connections, a working space of not less than 36-inches (914 mm) in width , 36-inches (914 mm) in depth and _________ inches (1981 mm) in height shall be provided and maintained in front of and around wall-mounted and free-standing fire department connections, except as otherwise approved (NYC Fire Code 2014 — 120, 912.3.2)
78-inches
In a sprinkler system, screwed unions may be used for pipe up to and including (NFPA 13, 2007 — 13030, 6.4.5.1)
2-inch diameter
In a sprinkler system, the pipes supplying sprinklers, either directly or through sprigs, drops, return bends, or am-overs are called (NFPA 13, 2007 — 13-19 3.5.1)
Branch lines
Where the capacity of isolated trapped sections of pipe is more than 5-gal (18.9-L) and less than 50-gal (189-L) an auxiliary drain shall consist of a valve ________ inch or larger and a plug or a nipple and cap (NFPA 13, 2007 — 13-38, 8.16.2.5.2.2)
1-inch
Where a fire pump is provided, a sign shall be located in the vicinity of the pump indicating the _______________ ______________and FLOW REQUIRED at the pump discharge flange to meet the system demand (NFPA 14, 2003 — S-66, 6.6)
Minimum pressure
Hand-held portable fire extinguishers having a gross weight exceeding 40-pounds (18-kg) shall be installed so that the top of the extinguisher is not more than ______ feet above the floor (NYC Fire Code 2014 — 116, 906.9.1)
5-feet
Of the following statements pertaining to sprinklers, the one that is most applicable to an upright sprinkler, is that an upright sprinkler is (NFPA 13, 2007 — 13-20, 3.6.3.6)
Installed in such a way that the water sprayed is directed upward against the deflector
A gauge that can be used to measure either vacuum or pressure is commonly called
Compound gauge
For schedule-40 and copper tubing, the minimum radius of a bend shall be ____________ for pipe sizes 2-inches (50-mm) and smaller (NFPA 13, 2007 — 13-29, 6.3.7.2)
6-pipe diameters
For schedule-40 and copper tubing, the minimum radius of a bend shall be _______________ for pipe sizes 2-1/2-inch (65-mm) and larger (NFPA 13, 2007, 13-29, 6.3.7.2)
6-pipe diameters
The pump capacity of a multistage centrifugal fire pump is rated on the (NFPA Fire Handbook — stationary fire pumps)
Discharge on one stage in gallons per minute
The ability of concrete to hold the studs varies widely according to type of (NFPA 13, 2007 — 13-276, A.9.1.3.9.3)
Aggregate / Quality of concrete / Proper installation
Powder-driven studs should not be used in steel of less than (NFPA 13, 2007 — 13-276, A.9.1.4.1)
3/16-in. total thickness
A storage method in which a number of tires are strapped together (NFPA 13, 2007 — 13-23, 3.9.4.1)
Banded tires
Pneumatic tires for passenger automobiles, aircraft, light and heavy trucks, trailers, farm equipment, construction equipment (off-the-road), and buses (NFPA 13,2007 — 13-23, 3.9.4.10)
Rubber tires
Tires stored horizontally or flat (NFPA 13, 2007 — 13-23, 3.9.4.5)
On-side tire storage
Tires stored vertically or on their treads (NFPA 13,2007 — 13-23, 3.9.4.6)
On-tread tire storage
The clearance from the top of storage to sprinkler deflectors shall be not less than ___________ where rubber tires are stored (NFPA 13, 2007 — 13-52, 8.5.6.5)
36-inches
The minimum temperature rating of ceiling sprinklers in general storage, rack storage, rubber tire storage, roll paper storage, and baled cotton storage application shall be (NFPA 13, 2007 — 13-48, 8.3.2.7*)
150 F
(#35)Columns within rubber tire storage, where fireproofing is not provided, steel columns shall be protected as follows (NFPA 13, 2007 — 13-184, 18.2.1, 18.2.2)
Storage exceeding 15-feet through 20-feet (4.6-m through 6-m) in height - one sidewall sprinkler directed to one side of the column at a 15-foot (4.6-m) level / Storage exceeding 20-feet (6.1-m) in height - two sidewall sprinklers, one at the top of the column and the other at 15-foot (4.6-m) level botoh, directed to the side of the column / The flow from a column sprinkler(s) shall be permitted to be omitted from the sprinkler system hydraulic calculations