Class 3 Flashcards
The distance between the floor and the underside of the roof deck within the storage area: (NFPA 13, 2007 — 13-22, 3..18)
Roof height
What is the minimum size ball drip permitted on a check valve: (NFPA 14, 2007 - - -S-28, 4.8.2.2 Q (i) - - - NFPA-14,2003 - - - S-50,4.8.2.2 (i) )
3/4-inch
The sprinkler pipes in which the sprinklers are placed, either directly or through risers: (NFPA 13, 2007 — 13-19 3.5.1)
Cross main
Class III standpipe systems shall be installed throughout the following building; in buildings 3-stories or more in height with floor area of: (NYC Building Code 2014, 905.3.1 (2), 214 - - - NFPA 14, 2003 - - - S-68A,905.3.1 (2) )
7,500-Sq. ft.
All the equipment, material and labor required for testing a system or parts thereof of a fire system: (NFPA 14, 2007, S-78, 11.1.3)
Installing contractors shall complete and sign appropriate contractor’s material and test certificate(s)
Express piping to high zone siamese connections shall not be installed in STAIRWAY enclosures but may be in any other: (NFPA 14, 2007 - - - S-S-29, 4.8.2.2Q(j)(1) - - - NFPA 14,2003 - - - S-50, 4.8.2.2(i)(j) )
Protected shaft
Within a year a certain material rose from $250.00 to $270.00 for the same quantity. The percentage price increase was:
8%
Unless the requirements of 6.7.3.1, 6.7.1.3.2 or 6.7.1.3.3 are met, all valves controlling connections to water supplies and to supply pipes to sprinklers shall be listed: ( NFPA 13,2007 — 13-32, 6.7.1.3 & 3.1*-)
underground gate valve equipped with a listed indicator post / indicating valves
On a set of drawings a line is drawn 12-1/2-inch long. If the scale is 1/8 of an inch to the foot, what is the actual length of the pipe
100-feet
The main reason why the outer ends of all external and internal screw threads for a firehouse connection are terminated by a higbee-cut-blunt start on a full thread is to:
To avoid cross threading of the threads
Each two-way fire department connection for standpipe systems shall be provided with caps painted: (NFPA 14, 2007, S-46, 6.4.2Q)
Red
Horizontal piping from the standpipe to hose connections that are more than _____ (457-mm) in length shall be provided with hangers: (NFPA 14, 2003, S-66, 6.4.2.1)
18-inches
Class 1 and class 111 standpipes in building with floor heights less than 150-feet (45 720-mm) above grade plane shall be at least: (NFPA 14, 2007 - - - S-53, 7.6.1Q - - - NFPA 14,2003 - - - S-71, 7.6.1 and S-71, Table 1)
4-inches in diameter
The nominal pipe size of the pipe refers to the pipes:
Area of pipe
(18) In the sentence “ the working drawings shall be coordinated with…” in the above paragraph. The word coordinate means most nearly:
In agreement
Mains supplying risers or cross mains: (NFPA 13, 2007 — 13-19, 3.5.3)
Feed Main
Bolts shall be provided with a: (NFPA 13, 2007 — 13-93, 9.1.1.6.8)
Flat washer / Nut
The vertical supply pipes in a sprinkler system: (NFPA 13, 2007 — 13-19, 3.5.5)
Riser
According to the N.Y.C. Building code the maximum number of sprinkler heads that a N.Y.C. Master PLumber is authorized to install on any one building off a domestic water line: (“Plumbing work”)
30
Two pipes are running full of water and going into one pipe. One pipe is carrying 47-gallons of water per minute and the other Carrying 53-gallons of water per minute. What is the amount of water coming through the third pipe
100-gallons/minute
Which document established the minimum requirements for the periodic inspection, testing, and maintenance of water-based fire protection systems and the actions to undertake when changes in occupancy,use, process, materials, hazard, or water-supply that potentially impact the performance of the water-based system are planned or identified:
NFPA 25
Of the following type of hangers, the one that is most commonly used in piping work is the: (NFPA 13,2007 — 13-277)
Clevis- Hanger type
Riser control valve in standpipe systems, shall where practicable, be located within required stair enclosure serving the: (NFPA 14, 2007 — S-41, 6.2.2Q(1) — NFpa 14, 2003 — S-59, 6.2.2 (1) )
Entrance floor
An air compressor is primarily used for: (NFPA 13,2007 - - - 13-34, 7.2.6.2*)
Forcing water through fire sprinklers in a building
Upon reading question #61, the valves on the suction side and the discharge of the fire pump shall be deemed to comply with this requirement when the discharge valve is placed on the discharge side of the: (NFPA 14, 2007 — S-40, 6.3.1.1Q — NFPA 14, 2003 — S-59, 6.2.1)
Check valve
Of the following types of heat detectors the one that does not initiate an alarm when the detecting element reaches a predetermined set temperatures is known as: (NFPA 72, 2002—- 72-17, 3.3.43.16*)
Rate-of-rise-detector
When cutting or welding, the clothing that is worn should: (OSHA rules)
Include flame resistant gloves and aprons
Test 3.1 Question
Answer
O.S.H.A. Is an abbreviation for an administration that deals primarily:
Workplace health and safety
Standpipe risers supplied by an upper level criss connection shall be provided with manual control valves or remote-control valves, so arranged that risers supplied by the upper level cross connections may be shut off from the tank supplies: (NFPA 14, 2007 - - - S-51, 7-5Q (3) - - - NFPA 14, 2003 - - - S-70,7.5 (3) )
Independently
A class 11 standpipe system provides ______ hose stations to supply water for use primarily by building occupants or by the fire department during initial response: (NFPA 14, 2007 — S- 35, 5.3.2.1)
38-mm (1-1/2-inch)
Holes for bolts shall not exceed _______ greater than the diameter of the bolt: (NFPA 13, 2007 — 13-93, 9.1.1.6.7)
1/4- inch
The pump capacity of a multi-stage centrifugal fire pump is rated under:
Discharge of one stage in gallons per minute or L/m
Of the following plumbing and sprinkler statements, the one that is most correct concerning the function of the License Board: (Admin. Code 2014, 28-401.3, page 87)
Advising the commissioner regarding the character and the fitness of applicants for a license or certificate of competence / Advising the commissioner regarding allegations of illegal practices by persons licensed / Advising the commissioner regarding other matters in the industry as the commissioner may see fit
(17) In the sentence “all work indicated schematically in the drawings..” in the above paragraph. the word schematically means most nearly:
An outline
Underground piping supplying a standpipe system shall be flushed in accordance with NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances. piping between the fire department connection and the check valve in the inlet pipe shall be flushed with sufficient volume of water in order to remove any obstruction debris and trash accumulated in the piping prior to the completion of the system and ___________________: (NFPA 14,2007, S-78, 11.2.1, 11.2.2)
prior to the installation of the fire department connection
Two-way fire department connections shall be of the flush or freestanding type, with the exception of the swivel caps, shall not project beyond the street property line. the riser pipe to a free- standing two-way fire department connection shall be: (NFPA 14, 2007 — S-28, 4.8.2.2(g) (2) — NFPA 14, 2003 — S-49, 4.8.2.2(g) (2) )
Red brass pipe
Two-way fire department connections shall be provided in maximum two-way fire department connection zone heights if 600-feet, supplying no more than two standpipe zones. A normally ________ valved interconnection shall be provided between each two-way fire department connection zone: (NFPA 14,2007 - - - S-28, 4.8.2.2Q (j) - - - NFPA 14,2003 - - - S-50, 4.8.2.2(j) )
Closed
In the installation of signs in a standpipe system, the signs shall be secured to a device or building wall with corrosion- resistant: (NFPA 14, 2007, S-47, 6.6 — NFPA 14, 2003 — S-66, 6.5)
Chains / Fasteners
(33) During the contraction, the installation approval has been granted to change the location if several components of the fire alarm system. The net effect of this change is a savings of $550.00 in cost to the prime contractor. If the contract was originally for $12,375.00 then according to the provisions if the above paragraph the adjusted contract dollar value then becomes
$12,100.00
Valves in standpipe systems shall be readily accessible for inspection,repair and use. if the valve is placed so that its operating mechanism is more than 7-feet above a floor or stair landing, a ______ wide wrought iron, steel or equivalent ladder securely fastened shall be provided for access to the valve: (NFPA 14,2007 — S-42, 6.2.2Q(5) — NFPA 14, 2003 —- S-60, 6.2.2(5) )
12-inch
Sprinklers shall be inspected from the floor level: (NFPA 25,2014 — 25-15, 5.2.1.1*)
Annually
Post installed (expansion shields) shall not be used in ceilings of: (NFPA 13, 2007 — 13-94, 9.1.3.3)
Concrete
A test of a closed piping system and its attached appurtenances consisting if subjecting the piping to an increased internal pressure for a specified period of duration to verify system integrity and leak rates: (NFPA 25, 2014 - - - 25-9, 3.3.20)
Hydrostatic test
In a standpipe system each control valve shall be conspicuously marked with a number assigned to it on the ____ ____ for the standpipe: (NFPA 14, 2007 — S – 42, 6.2.2Q (6) — NFPA 14, 2003 — S-60, 6.2.2(6))
Riser diagram
A specification of a sprinkler head is stated as a model FF 1/2” or fire 1/2” NPT Upright & Pendent the letters NOT refer to:
Thread designation of the sprinkler head
A class 111 standpipe system provides _______ hose stations to supply water for use by building occupants and ________ hose connections to supply larger volume of water for use by fire departments and those trained in handling heavy fire streams: (NFPA 14, 2007, S-12, 3.3.15.3, See: Fig #1)
38-mm (1-1/2-inch), 65-mm (2-1/2-inch)
Any sprinklers that shows sign of the following shall be replaced:( NFPA 25,2014 — 25-15, 5.2.1.1.2)
Loading / Leakage / Corrosion
The oxygen cylinders used in an oxy-acetylene system are made out of
Steel
wood screws shall be installed with (NFPA 13, 2007 — 13-217, 22.4.4.11)
Screwdriver
Of the following statements pertaining to sprinklers the one that is most applicable to a upright sprinkler is that an upright sprinkler: (NFPA 13, 2007 — 13-20, 3-6.3.6)
To be installed in such a way that the water sprayed is directed upwards against the deflector
The color of the caps on each fire department connection of a combination standpipe and sprinkler system: (NFPA 14, 2007, S-46, 6.4.5.2Q - - - NDPA 14,2003, S-64, 6.3.5.2)
Yellow
The outside diameter of “K” copper is always:
Larger than its nominal size
In the installation of a centrifugal fire pump, under such vibrant pump suction, flanged are not the same size, it is recommended that in practice, they be connected with a: (NFPA 20, 2013, 20-62, Figure A.4.14.6 - - - 20-16, 4.14.6.4)
Flange eccentric reducer
A suppressor used in a fire piping system is used for:
Controlling vibrations
if you worked a 7-1/2-hour/dat, and you worked a 5-day week, and make $10.00/hour and you worked 16-hours overtime at $15.00/hour, what would be your gross pay
$615.00
All electric wiring contained in a fire alarm system in a fire suppression system must be installed in accordance with:
NYC electrical code
Test 3.5 Question
Answer
The maximum pressure at any point in the standpipe system at any time shall not exceed 24.1 bar (350 psi), except for piping to high zone two-way fire department connections, and shall not, in any case, be greater than the pressure rating of the system components in accordance with section 4.2 of this reference standard NFPA 14,2007. Maximum height oer zone is limited to: (NFPA 14,2007 - - - S-48, 7.2Q)
300-feet
The minimum spare sprinklers that must be kept in stock upon completion of the installation of a sprinkler system that contains 375: (NFPA 13, 2007 — 13-28, 6.2.9.5)
12
(47)Each two-way fire department connection shall be connected to a riser or to a cross connection connecting other two-way fire department hose connections or risers within each two-way fire department zone provided in accordance with section 4.8.2.2. The pipe from the two-way fire department connection to the riser or cross connections shall be: (NFPA 14,2007 - - - S-52, 7.5Q (6) - - - NFPA 14,2003 - - - S-71, 7.5(6) )
5-inch
All piping to water motor-operated devices shall be galvanized or brass or other corrosion-resistant material acceptable under this standard and of a size not less than: (NFPA 13,2007 — 13-33, 6.9.3.3)
3/4-inch (19-mm)
Unless permitted by 9.1.1.4 or 9.1.1.4.3, the components of hanger assemblies that directly attach to the pipe or the building structure shall be listed. Mild steel hangers formed from rods shall be: (NFPA 13, 2007 — 13-92, 9.1.1.4.1 & 2)
Shall be listed
Where slip-on flanges are welded to pipe with a single fillet weld, the weld shall be on the hub side of the flange and the minimum throat weld thickness shall not be less than _________ times the pipe wall thickness or the hub thickness whichever is less: (NFPA 13,2007 - - - 13-31, 6.5.2.4.3)
1.25
The maximum pressure at any point in the standpipe system at any time shall not exceed ____ psi, except for piping to high zone two-way Fire department connections, and shall not, in any case, be greater than the pressure rating of the system components in accordance with section 4.2 of the reference standard. Maximum height per zone is limited to _______ feet: (NFPA 14, 2007, S-68, 7.2Q — NFPA 14, 2003, S-68, 7.2*)
350, 300
Waterflow alarm apparatus shall be listed for the service and so constructed and installed that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler of the smallest orifice size installed on the system will result in an audible alarm on the premises with ______ after such flow begins until such flow stops: (NFPA 13,2007 — 13-32, 6.9.1)
5-minutes
Of the following terms, the one which is not generally used to describe a type of payment to a contract for work performed:
Security payment
Test 3.4 Question
Answer
The aboveground horizontal or vertical pipe between the water supply and the main (cross or feed) that contains a control valve (either directly or within its supply pipe) and a water flow alarm device: (NFPA 13, 2007 — 13-19, 3.5.8)
System riser
After cutting, pipe ends shall have: (NFPA 13,2007 — 13-32, 6.5.6.1)
Burrs removed/ Fins removed
Class 1 standpipe systems in buildings classified as high-rise buildings shall be: (NFPA 14,2007 - - - S-36, 5.1.2Q - - - NFPA 14, 2003 - - - S-54, 5.4.1.2)
Automatic wet
All sprinkler piping must be drained in a dry pipe system; if the pipe was pitched at a rate of 1/2-inch/10-feet and you have a 275-foot run, how much would the pipe drop
13.75-inches
A set of sprinkler heads and pipe plans are drawn to scale of 1/4-inch per foot. A horizontal line measuring 12-3/4- inch is on the plan. The actual measurement should be:
51-feet
A suppressor used in a piping system is never used for:
Supporting the weight of the piping system
Who is responsible for properly maintaining a water-based fire protection system: (NFPA 25, 2014 - - - 25-13, 4.1.1)
The property owner / the designated representative
The size of a listed dial spring pressure gauge shall be connected to each discharge pipe from the fire pmp and the public waterworks at the pressure tank, at each amin drain connection at the aire pump supplying the pressure tank, and at the top of each standpipe: ( NFPA 14, 2007, S-37, 5.5.1 — NFPA 14, 2003, S-55, 5.6*)
3-1/2- inch
The installing contractor shall provide a sign identifying the basis of the system as either hydraulic calculations or _______: (NFPA 13,2007 —- 13-31, 6.5.4.3)
H.P.D
Solder joints shall be permitted for wet pipe systems in light hazard and ordinary hazard (Group 1) occupancies where the piping is ______ irrespective of sprinkler temperature ratings: (NFPA 13, 2007 —- 13-31, 6.5.4.4)
Exposed
When placing an extension ladder against a straight wall the ladder must be placed at a safe angle against the wall, therefore, the recommended practice, the distance the foot of the ladder from the wall would be approximately equal to: (OSHA’s compliance encyclopedia, page 740-11 “General Industry Standards”
1/4 the length of the ladder