Torch cutting and welding if sprinkler piping shall: (NFPA 13, 2007, 13-30, 6.5.2.2.5, NFPA 13,2002,13-26, 6.5.2.12)
Not be permitted as a means if modifying or repairing sprinkler systems
When welding is performed on sprinkler piping the following procedures shall be completed: (NFPA 13, 2007, 13-31, 6.5.2.4.6, NFPA 13,2003, 13-36, 6.5.2.9 (1)(2)(4) )
Holes in piping outlets shall be cut to the full inside diameter of fittings prior to welding in place of the fittings prior to welding in place of the fittings / Discs shall be retrieved / Fittings shall not penetrate the internal diameter of the piping
According to the ASME B1.20.1, the number of threads per inch that properly threads a 2-inch pipe should have: (NFPA 13, 2007, 13-30, 6.5.1.1, NFPA 13, 2002 - - - 13-26, 6.5.1.1)
11-1/2-threads per inch
Of the following types if valves an indicator valve would be:
Butterfly valve
When an oxy-acetylene torch is used for making a brazed joint the type if flame that should be used is:
Reducing flame
The limiting length that determined whether a length of pipe that is threaded on both end is considered either as cut pipe or nipple is:
12-inch
Listed indicating valves shall not close in less than ________ when operating at maximum possible speed from the fully open position: (NFPA 13, 2007, 13-32, 6.7.1.2,, NFPA 13, 2002 - - - 13-27, 6.7.1.2)
5-seconds
A welding procedure shall be prepared and qualified, before any welding is done, for all welding installed in a fire suppression piping system: (NFPA 13,2007, 13-31, 6.5.2.5.1, NFPA 13, 2002 - - - 13-26, 6.5.2.13.5 and 6.5.2.13.6)
The licensed master fire suppression piping contractor / Fabricators
Of the following types of copper tubing the one that has the greatest wall thickness:
Type “K”
In order for a synchronous motor to operate properly a motor must be supplied with:
Both A.C. and D.C.
Of the following classifications of electrical motors a general purpose motor that would most likely be used where operating conditions are relatively clean and dry is the:
Open drip-proof motor
Soldered joints shall be permitted for _____ wet pipe systems in light hazard occupancies where the temperature classification of the installed sprinklers is of the ordinary-or intermediate-temperature classification: (NFPA 13,2007, 13-31, 6.5.4.3, NFPA 13,2002 - - - 13-27, 6.5.4.3)
Exposed
Solder joints shall be permitted for wet pipe systems in light hazard and ordinary hazard (Group 1) occupancies where piping is ____________, irrespective of sprinkler temperature ratings: (NFPA 13, 2007, 13-31, 6.5.4.4NFPA 13, 2002 - - - 13-27, 6.5.4.4)
Concealed / Exposed / Non-exposed
Of the following types of filler metals for brazing the one which can produce highly toxic fumes when brazing:
Bag-2
Waterflow alarm apparatus shall be listed for the service and so constructed and installed that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler of the smallest orifice size installed in the system will result in an audible alarm on the premises within _____ after such flow begins and until such flow stops: (NFPA 13, 2007 - - - 13-32, 6.9.1)
5-minutes
In sprinkler systems, all control, drain and test connections valves shall be provided with: (NFPA 13,2007, 13-32, 6.7.4.1)
Permanently marked weatherproof metal / Rigid-plastic identification signs
Of the following types if heat detectors the one that is commonly used in automatic sprinkler and often used to release fire is the: (NFPA 72, 2002, 72-16, 3.3.43.7 & 72-112, A 3.3.43.7)(“NFPA Fire Handbook”Automatic fire detectors”)
Fixed-Temperature-detector
Seamless steel pipe has been specified to be used in the installation of a sprinkler system. The maximum distance between hangers for supporting a horizontal 1-inch diameter pipe: (NFPA 13,2002 - - - 13-85, Table 9.2.2.1)
12-feet
For class 1 and class 111 systems, the minimum flow rate for the hydraulically most remote standpipe shall be: (NFPA 14, 2003, S-76, 7.10.1.1.1)
500-gpm
In the installation of a centrifugal fire pump when the suction pump and suction flange are not the same size it is recommended practice that they be connected with:(NFPA 20, A-9.6)
Eccentric flanged eccentric reducer
Of the following statements pertaining to sprinklers the one that is most applicable to an upright sprinkler is that an upright sprinkler: (NFPA 13, 2007, 13-20, 3.6.3.6, NFPA 13,2002 - - - 13-17, 3.6.3.6)
Installed in such a way that the water sprayed is directed upward against the deflector
Of the following statements pertaining to sprinklers, the one that is most applicable to a pendant sprinkler, is that a pendent sprinkler is designed to be: (NFPA 2007, 13-20, 3.6.3.3, NFPA 13,2002, 13-17, 3.6.3.3)
Installed in such a way, that the water stream is directed downward against the deflector
A sprinkler in which all or part of the body, other than the shank thread, is mounted within a recessed housing: (NFPA 13,2007, 13-20 3.6.3.4, NFPA 13, 2002, 13-17, 3.6.3.4)
Recessed
A sprinkler system employed automatic sprinklers attached to a piping system containing water and connected to a water supply so that water discharges immediately from sprinklers opened by heat from a fire: (NFPA 13, 2007, 13-19, 3.4.10)
Wet pipe sprinkler system
Test 2.2 Question
Answer
During construction, the installation approval has been granted to choose the location of several components of the fire alarm system. The next effect of this change is a savings of $550.00 in cost to the prime contractor. If the contract was originally for $12,375 then according to the provisions of the above paragraph the adjusted contract dollar value then becomes:
550 / 2= 275 - 50% = 12,375 - 275 = $12,100.00
In the sentence “ there shall be no waiver of rights” the word waiver means most nearly:
Revoking
In the phrase “all rights reserved upon approaching authorities to change” the word reserved means most nearly:
Kept
In the phrase “to change the location” of appurtenances to accommodate conditions. The word accommodate means most nearly:
Satisfy
The pump capacity of a multistage centrifugal fire pump is rated on the: (notes: Stationary fire pumps, NFPA 20)
Discharge of one stage in gallons per minute
The main reason why the outer ends of all external and internal screw threads for a fire hose connection are terminated by a hinge cut blunt start on a full thread is to:
To avoid cross threading of the threads
Of the following type of fire standpipe systems, is a standpipe system, that does not have a permanent water supply attached to the system: ( NFPA 14,2007 - - - S-35, 5.2.4* - - - NFPA 14, 2003, S-53, 5.2.4)
Manual-Dry
When black pipe has been specified to be used in installation of a pimple standpipe system, the maximum allowed horizontal spacing between hangers’: (NFPA 13, 2007, 13-97, Table 9.2.2.1(a) - - - NFPA 14, 2003, S-66, 6.4.2.2)
15-feet
The amount of water to extinguish a fire depends on the: (NFPA Fire Handbook, Characteristics & Hazards of water & water additives)
Heat output (BTU) of the fire
How quickly a fire is extinguished depends on how the water is applied, how much is applied and: (NFPA Fire Handbook)
In what form water is applied
To achieve extinguishment by cooling, it is best to apply water so that the maximum amount of: (NFPA Fire Handbook)
Heat will be absorbed
Water absorbs more heat when it is converted to: (NFPA Fire Handbook)
Steam
When water is absorbed into steam, it will absorb the most heat when used from: (NFPA Fire Handbook)
Small droplets (spray)
(14)Latent heat (thermal energy absorbed) of fusion (transition of a substance from a solid to a liquid) is the amount if energy required to change the state of water from a solid (ice) 32 F, (0 C) to a liquid. Using this process water absorbs:
143.4-BTU per pound
(15)Water is effective as a cooling agent because of its high latent heat (thermal energy absorbed in a process other than change of temperature) of evaporation (changing water from a liquid to vapor) which is: (NFPA Fire Handbook)
970.3-BTU per pound
With the information given in question #14 and #15, and we change a pound of water in a solid state of ice to steam(vapor), the amount of BTU’s required would be:
1294-BTU per pound
When water expands from its liquid state to a vapor state its volume increases:
1600 to 1700-times that of a liquid
At ordinary temperatures, water exist as a stable liquid. Water viscosity (the quality of sticking or adhering) in the temperature range of 34 to 210 F remains consistent which allows it to be:
Transported and pumped
Life safety considerations must be weighed when choosing an effective fire extinguishing agent. Water as an agent is safe, no-toxic, non-corrosive, and stable. Water remains stable when applied to a fire and does not break down into its basic elements. The chemical symbol for water: (NFPA Fire Handbook)
H-2-O
The chemical symbol for oxygen: (NFPA Fire Handbook)
O