CHEMICAL FEED SYSTEM Flashcards

1
Q

_____________________ is applied by the Chemical Feed System and used as a biocide in conjunction with bleach in the cooling towers. (Ref: 2.2 CF SD)

A

Sanibrom

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The sulfuric acid chemical feed skid pumps are automatically controlled to maintain a ______________ setpoint. (Ref: 2.4.2 CF SD)

A

pH

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

__________________ uses a fluorescent tracer dye to monitor the concentration in the cooling tower. The tracer dye is measured by a little dipper probe to maintain the proper inhibitor concentration. (Ref: 2.4.2 CF SD)

A

Aqua Serv 4933AD

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Nalco 8735 is used to raise the pH of the boiler water to between _______________ and alkalinity above 100 ppm. (Ref: 2.5.2 CF SD)

A

10.5 and 12.0 pH

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The feed rate for chemicals applied to the deaerator storage tanks and the main steam header is controlled __________________. (Ref: 4.1 CF SD)

A

manual pump adjustments based on chemical testing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly