Chapter 9 Flashcards
4 main types of sprinkler systems:
Wet Pipe
Dry Pipe
Deluge
Pre-action
According to NFPA statistics, about ___% of fires in sprinklered building are either extinguished by the sprinklers or held in check until they can be completely extinguished by the FD.
96%
The ___ is an indicating valve; at a. glance a FF can tell if it is open or closed. Typically is located just under the sprinkler alarm valve.
Main valve
3 types of control valves:
Outside screw and yoke
Post indicator valve
Wall post indicator
___: Threaded stem is showing(___) not showing(___) and is the most common main water control valve.
Outside screw and yoke
Open
Shut
___: Stem is inside a post; a window shower whether ___ or ___.
Post indicator valve
Open or shut
___: Generally the same as post indicator valve but protrudes from the wall.
Wall post indicator
___ valves are for both system drainage and alarm silencing.
Stopcock valves
___ valves are used for system drainage and as test valves.
Global valves
The ___ valve is used to simulate actuation of the sprinkler system to ensure it is working properly.
Test/inspector valve
The ___ can also be used to test the system, much like the alarm test/inspector valve.
Main drain
The water flow alarm is either ___ or ___.
Electronic or Hydraulic
Water flow alarm… In hydraulic alarms water actually drives the ___, it is a local alarm that alerts building personnel.
Alarm gong
Water flow alarm… In electronic alarms the water presses against a diaphragm that activates the alarm. Can be a ___ alarm, or it can be connected to a ___ that can notify the fire department when the alarm is activated.
Local alarm
monitoring company
Water supply for sprinklers must be ___, ___, and of adequate ___.
Reliable
Automatic
Volume and pressure
The flow must be able to provide a minimal residual water press use of ___ psi tote highest and farthest sprinkler head.
15 psi
An indication that a fire pump is present is a ___; which looks like a wall hydrant that has multiple ___ inch outlets; the number of outlets is determined by the ___ for the occupancy.
Test Header
2.5”
Required flow
On sprinklers with a single riser, the FDC is connected to the ___ side of the system.
Sprinkler side
On a multiple riser system, the FDC is connected to the ___ side of the system.
Supply side
On a multiple riser system, the FDC is connected to the supply side of the system, thus the flow can be controlled by shutting down the ___ valve.
Main water control valve.
Because dry pipe systems take longer to deliver water, many have ___ or ___ to speed up the process.
Accelerators or exhausters
___: Like a dry pipe but additional alarm equipment must be activated before the pipes will with water; then a sprinkler head must still be activated to flow water.
Pre action sprinkler system
Sprinkler system used in areas where water damage must be avoided.
Pre action system
___: like pre action, has separate additional equipment. Typically used in locations where the occupancy is extra hazardous.
Deluge system