Chapter 8 - storage of cylinders awaiting use, resale, or exchange Flashcards
The quantity of LP gas in cylinder, stored or displayed, shall not exceeded _______ in one location, with an additional storage separated by ______
200 pounds, 50 feet
The maximum quantity to be stored in one building shall shall not exceed:
1000 pounds
Storage of cylinders within a residential building, including the basement or any storage area in a common basement or multifamily building and attached or detached garages, shall be limited to cylinders with a maximum water capacity of
2.7 pounds
Storage outside of buildings for cylinders awaiting use or resale or that are part of a cylinder exchange point shall be at ______ Away from any doorway, or opening in the building frequented by public or occupants, have at least two means of egress
At least 5 feet
Storage outside of buildings for cylinders awaiting user resale shall be ______ from any doorway or opening in a building or sections of a building that has only one means of egress
10 feet
Storage outside of buildings for cylinders awaiting use or resale shall be at least _______ from any automotive service station fuel
20 feet
Cylinders at a location open to the public shall be protected by either of the following:
An enclosure in a coordinates with 6.19.4.2 or a lockable ventilated enclosure of metal exterior construction
Retail cylinder exchange location shall be provided with at least one portable fire extinguisher, having a maximum capacity of 10 pounds dry chemical with an
ABC rating
Retail cylinder exchange locations, having at least one portable fire extinguisher with a maximum of 10 pounds of capacity dry chemical with an ABC rating shall not store more than
720 pounds of propane