Chapter 6 installation of LP – gas systems Flashcards
LP gas containers Shall be located ____________ unless they are specifically allowed to be located inside of buildings
Outside of buildings
LP gas containers shall be allowed in buildings only if containers are less than ______ water capacity for the purposes of being filled in buildings or structures complying with chapter 10
125 gallons
LP gas containers shall be allowed in buildings for cylinders awaiting ________, ________, or _________ when stored in a coordinates with chapter 8
Use, resale, or exchange
LP gas containers shall be allowed in buildings for containers on LP gas _________ garage in a coordinates with section 11.16
Fuel vehicles
LP gas containers shall be allowed within buildings if the containers use with LP gas ____________ comply with 11.15.1
Portable engine fuel systems
No part of an underground or mounded ASME container shall be ________ from a building or line of adjoining property that can be built upon
10 feet
The distance between containers shall be a minimum of ______ the sum of diameters of a adjacent containers
1/4
The distance for above ground containers from 125 gallons to 500 gallons Shall be, no less than _______ away from buildings and lines of adjoining property that can be built upon
10 feet
The distance between a building and an above ground container less than 125 gallons Is equal to
0 feet
All underground containers, larger than 2000 gallons are required to be a minimum of ______ from other containers important buildings in line of adjoining property
50 feet
All underground containers from one to 2000 gallons are required to be a minimum distance away from buildings and property lines
10 feet
Cylinders shall not be installed or located underneath any buildings unless the space is open to the atmosphere for ___________ of its perimeter or more.
50%
When containers are installed parallel within ends in line, the number of containers in one group:
Shall not be limited
Combustible materials should not accumulate or be stored within ________ of a container
10 feet
The minimum horizontal separation between above ground LP – gas containers and above ground tanks containing liquids, having flashpoint below 200°F shall be
20 feet
All above ground containers shall be
Painted
Cylinders shall not be in direct contact with
The soil 
Steel supports should be protected against fire exposure with a material that has a fire resistance rating of at least _____
Two hours
Continuous steel skirts that have only one opening that is ________ or less in diameter shall have fire protection applied to the outside of the skirts
18 inches
Underground containers installed in areas with no vehicular traffic Shall be installed at least
6 inches below grade
For underground tank installations within 10 feet of a public vehicular, thorough, fair or designed parking location, a non-interchangeable underground container shall be installed
18 inches below grade
If 18 inches below grade cannot be attained for an underground tank subject to vehicular traffic
A vehicular barrier shall be provided
Approved interchangeable above ground underground container, assemblies installed underground shall not be placed with the container shell more than ________ below grade
12 inches
The installation of a buried container shall include protection for the container and piping against ____________ from vehicular traffic
Physical damage
Prior to digging, the location of underground and mounded containers and piping in the vicinity of construction and excavation activities shall be determined in the installation shall be
Protected from damage
Where a container is to be abandoned underground, as much LP liquid gas as practical shall be removed through the container at the
Liquid withdrawal connection
Where the container is to be abandoned underground as much of the remaining LPG vapor as practical shall be removed through a
Vapor connection
Where a container is to be abandoned underground, the vapor shall be either recovered, burned,
Or vented to the atmosphere
Where a container is to be abandoned underground, where only vapor LP gas at atmospheric pressure remains in the container the container shall be filled with
Water, sand, or foam plastic
The discharge of the regulator vent shall be above the
Highest probable water level