Concentration of the lithium bromide can be most easily controlled by which of the following means?
Controlling the temperature in the generator
During seasonal start-up when should the purge pump be started?
30 minutes after start-up
Crystalization in a lithium bromide absorption refrigeration system is undesirable because it:
can block piping and passages, and can restrict flow
The low pressure side of a lithium bromide absorption chiller consists of what two parts?
evaporator and absorber
The vapour pressure of a solution depends on:
the temperature of the solution, and the concentration of the solution
How is crystallization in a lithium bromide absorption chiller prevented during shutdown?
put the unit through a dilution cycle
A dilution cycle is performed during the shutdown of an absorption refrigeration system to prevent?
crystallization
The concentration of lithium bromide will chance during the absorption of?
Water vapour in the absorber
How many pumps are there in a lithium bromide absorption chiller?
3
If a saturated solution is heated?
it will become unsaturated
Pump bearings in a lithium bromide absorption chiller may be made of plastic or?
carbon
Octyl alcohol is added to lithium bromide solution to:
act as a wetting agent
The high pressure side of a lithium bromide absorption chiller consists of what two parts?
generator and condenser