The noise levels of generators sized 5Kw to 200 Kw range from how many decibels from 25 feet?
25 dBa- 93 dBa
Single hearing protection is needed for noise less than how many dBa?
84 dBa
Double hearing protection is needed for noise levels greater than how many dBa?
104 dBa
Generators must not be closer than how man feet to a load because of noise,fire hazard, and air circulation?
25Ft
A generator set should not be operated while inclined more than how many degrees from level?
15 degrees
The annual load factor of a well operated active base should be 50% or more with a power factor of what percent or higher?
80%
Practically all general-purpose lighting in the U.S and at U.S overseas bases is how many volts?
120V
What is the sum of the rated capacities of all electrical appliances, lamps, motors, and so on connected to the wiring of the system?
Connected load
What is the ratio between the actual maximum demand and the connected load called?
Demand factor
Shelters should have additional windows or doors installed in localities where the summer temperatures exceed what temperature at any time?
80°F
Exhaust piping inside a building has to Be covered with insulation capable of withstanding a temperature of how many degrees?
1500°F
A ground rod must have a minimum diameter of 5/8 inches if solid or what size of pipe?
3/4 inches
A ground plate must have a minimum area of how many square feet and, where practical, be embedded below the permanent moisture level?
2
The National Electrical Code states that a single electrode consisting of a rod, pipe, or plate that does not have resistance to ground of how many ohms or less will be augmented by additional electrodes?
25
All electrical generators operating at how many volts or less must be solidly grounded?
600V