CDS - Life Safety Flashcards
OCCUPANT LOAD CALC’D FOR LIFE SAFETY REQ’S
the MINIMUM number of people you have to provide life safety features for; occupant load can alter Life Safety requirements (ex. capacity of means of egress, number of means of egress, emergency lighting, fire alarm, sprinkler system reqs.); NFPA
COMMON PATH OF EXIT TRAVEL AND DEAD END
common path of exit travel is typ. 75’ max. from any one point in the building to the location where there are at least 2 choices for exiting the building; entire length of travel to this point (NOT to the door) must be less than 75’; if bldg. is fire sprinklered, can be 100’
TRAVEL DISTANCE TO AN EXIT
200’; from any point within a room in a building, you must reach an exit within 200’; door to exit door shall be less than 150’ (2012 Life Safety Code, CMS)
STAIR; STAIR DOOR CHANGING SIZES
can never get smaller in your path of travel; min. req. for width of stair (48”) calc.- occupant load of entire floor x .3 = # of inches in width required (if less than 48”, use 48”; min. req. for width of door (36”), calc. - occupant load of entire floor x .2 = # of inches in width required; when above grade stair meets below grade stair at grade level, add the two req’d calculated widths to size the doors at each location/exit
STANDPIPE
it is a type of rigid water piping which is built into multi-story buildings in a vertical position, to which fire hoses can be connected, allowing manual application of water to the fire. Within buildings standpipes thus serve the same purpose as fire hydrants. They are required inbuildings that are 3+ stories and they should be operational during construction
WET STANDPIPE
it is filled with water from a public supply and is pressurized at all times and they can be used by building occupants
DRY STANDPIPE
is only used when needed for fire fighting; not file with water and not connected to a constant water supply; fire engines supply the water to the system
COMBINATION STANDPIPE
a combination of wet and dry standpipe
ANSI STANDARDS FOR ELEVATOR CARS
- 36in wide door 2. 54in high control buttons 3. Tactile control indicators; no turnaround space required; any finish floor material can be used; if carpet is used, max. pile height is .5in
NUMBER OF EXITS
1 exit: up to max. occ. load; 2 exits: more than max. occ. load; 2 exits: common path of egress travel more than the limit of travel in code; 3 exits: occ. load between 501-1000; 4 exits: occ. load is 1001+
DISTANCE BETWEEN EXIT DOORS
Non-Sprinklered Bldg: 2 exits that are placed apart 1/2 diagonal distance of the room; Sprinklered Bldg: 2 exits that are placed apart 1/3 diagonal distance of the room; if 3+ exits are req., at least 2 must conform with diagonal distance
WIDTH OF EXITS
stairways/exit corridor width: .03(occupant load) = # of inches, min. 44; egress openings/doors: .02(occupant load) = # of inches, min. 36
DEAD END CORRIDORS
limited to 20’; exceptions: can be 50’ depending on occupancy group; can have corridor longer than 20’ if the length is less than 2.5 times its width at the narrowest point
EGRESS DOORS
- readily distinguishable 2. readily recognizable 3. cannot be covered with mirrors or reflective surface 4. cannot be concealed fabrics, decorations, etc.; 36in min. with 32in clear width and 80in high min.; max. width of swinging doors in 48in; pivoted or side hinged; must swing in the direction of travel if occ. of 50+; cannot swing into a required travel path (can be recessed to avoid this problem)
EGRESS STAIRWAYS
must be completely enclosed 1-4 stories (1 hr rated walls and doors); 4+ stories (2 hr rated walls and 90min. rated doors)