What actions should be taken in the event of a major flammable liquid leak?
- Notify watchstander (call MILPOL) 9-5555
- Take Initial Action
A. Secure machinery
B. Wipe up liquids
C. Use AFFF to wash the bilge - If needed set main space/set box/take muster/wait for fire party
What actions should be taken in the event of a loss of control air pressure?
- Notify watchstander
- Secure compressed air isolation valve
- Secure control air isolation valve
- Restart air compressor if electrical control has tripled offline
What actions should be taken in the event of a class C fire in the switchboard?
- Notify the watchstander (call milpol)
- Secure 24V power to switchboard
- Ensure shoretie breaker is secured on pier (radio watchstander)
- Secure generators
- Should an EEBD
- Use CO2 extinguisher
- If needed set main space/set box/take muster/wait for fire party.
What actions should be taken in the event of a a class C fire in the SSDG?
- Notify watchstander (call milpol)
- Secure affected SSDG
- Ensure SSDG circuit breaker is open
- Ensue 120v condensation heater is open
- Shoulder an EEBD
- Use CO2 extinguisher
- If needed set main space/set box/take muster/wait for fire party.
What actions should be taken in the event of a SSDG overheating?
- Notify watchstander (call milpol)
- If temp so above 225 secure effected generator.
- Reduce the load.
What actions should be taken in the event of a SSDG overheating?
- Notify watchstander (call milpol)
- If temp is above 225 secure effected generator.
- Reduce the load
- Check for system intact
- Bring up off-line generator
- Parallel generators
- Place load on unaffected generator
- Place affected generator in idle
- Report system status
- If needed set main space/set box/ take muster/ wait for fire party
What actions should be taken in the event of an unusual noise or vibration in SSDG?
- Notify watchstander (cool milpol)
- Identify effected engine
- Secure effected engine
- Check system intact
- Report system status
- If needed set main space/set box/take muster/wait for fire party.
What actions should be taken in the event of a loss of lube oil pressure K the SSDG?
- Notify watchstander (call milpol)
- Secure effected engine
- Open the generator circuit breaker
- Report system status
- If needed set box/main space/ take mister/ wait for fire party.
What actions should be taken in the event of a loss of fuel oil pressure in SSDG?
- Notify watchstander (call milpol)
- Secure effected engine
- Open the generator circuit breaker
- Report system status
- If needed set main space/set box/take muster/ wait for fire party
What action should be taken in the event of a SSDF governor malfunction?
- Notify watchstander
- Open bus tie breaker
- Secure effected generator
- Open SSDG circuit breaker
What actions should be taken in the event of a toxic gas leak?
- Notify the watchstander (call milpol)
- Set the Toxic Gas Bill
- Secure the space
- Take a muster
- Don SCBA and investigate
What actions should be taken in the event of a SSDG overload?
1. Strip the electrical load A. Start with non-vitals (white) B. Next are the semi-vitals (Yellow) C. Last are the vitals (red). Require EO's Permission 2. If needed secure the SSDG