FDC signs shall not be less than how many inches in width and how many inches in height ?

A

4” W x 8” H

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Identification signs for all control, drain, test and alarm valves shall be of the standard design approved by who?

A

Fire Chief

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Fire hose cabinets shall be clearly identifialbe or contain a sign on the cabinet door stating “FIRE HOSE” with letters not less than how many inches height on a contrasting background ?

A

3 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

In regards to apartments, when shall the owner or responsible resident, reside on the premises ?

A

If apartment has 16 or more units

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

In regards to hotels, when shall the owner or responsible resident, reside on the premises ?

A

If hotel has 20 or more guest rooms

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Hose inside hose cabinets shall be what length ?

A

100 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Fire escape windows shall have a minimum of how many inches when open ?

A

29” inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Fire escape window sills shall not be more than how many inches above the floor and landing ?

A

30” inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Horizontal travel distance of travel to the nearest extinguisher shall not exceed how many feet ?

A

75 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Garden-type APARTMENT houses containing ____ or less units and not over _____ stories in height, do not require extinguishers

A

15 ; TWO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Garden-type HOTELS containing ____ or less units and not over _____ stories in height, do not require extinguishers

A

19 ; TWO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Roof obstruction exceptions:
Guy wires, rods, aerial or antenna masts m ay be attached ‘to a roof structure having a slope of less Than ___ degrees provided there is full clearance of ___ feet or more between the roof and said obstruction.

A

30˚ ; 7 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

EXTRA SPRINKLER HEADS:

For systems with not over 300 sprinklers, provide how many extra sprinkler heads ?

A

6

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

EXTRA SPRINKLER HEADS:

For systems with 301 to 1000 sprinklers, provide how many extra sprinkler heads ?

A

12

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

EXTRA SPRINKLER HEADS:

For systems with over 1000 sprinklers, provide how many extra sprinkler heads ?

A

24

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Gas pump shut off switch must not be closer than ____ feet nor farther than _____ feet away from any dispenser

A

15 feet; 100 feet

17
Q

Every auto fueling station has have on its premises at least how many separate portable fire extinguishers ?

A

Two

18
Q

No hose used for transferring Class I, II, or IIIA liquids from any fixed dispensing apparatus shall be more than ______ long, including nozzle.

A

14 feet

19
Q

Portable fire extinguishers having a gross weight not exceeding 40 pounds shall be installed so that the TOP of the extinguisher is not more than _______ above the floor

A

5 feet

20
Q

Extinguishers having a gross weight GREATER than 40 pounds (except wheeled type) shall be so installed that the TOP of the extinguisher is not more than _________ above the floor

A

3 1/2 feet

21
Q

Portable fire extinguishers should not be located where ambient temperatures exceed _______ Fahrenheit unless otherwise noted on the nameplate of the extinguisher.

A

120˚ F

22
Q

Any Storage Pile shall be limited to a maximum length of _____ feet

A

100 feet

23
Q

In unsprinklered buildings, piles of materials, tiers of shelving, or racks shall have their highest point at least ______ feet below the ceiling, lowest chords, beams, girders, or other roof support trusses which may obstruct the effective application of water from hose streams.

A

3

24
Q

In sprinklered buildings, piles of materials, tiers of shelving, or racks shall have their highest point at least ___ inches below automatic sprinkler heads

A

18” inches

25
Q

Where storage consists of large, tightly-packed piles of baled, sacked, or cased material, the distance below sprinkler heads shall be a minimum of ____feet.

A

3 feet

26
Q

Pallet piles shall be stored no higher than ____ feet

A

6 feet

27
Q

The storage height of pallets may be increased up to ____ feet in height provided the Storage Area meets the requirements of L.A.F.D. Standard No. 6

A

20 feet

28
Q

Drums or carboys shall not be stacked more than two containers high unless ______ . Maximum height shall be _____ feet.

A

On pallets; 12 feet

29
Q

in a basic commercial occupancy materials shall be stored a minimum distance of ____ inches away from light fixtures.

A

18 inches

30
Q

in a basic commercial occupancy in no case shall the clearance between the bottom of a portable fire extinguisher and the floor be less than:

A

4 inches

31
Q

a basic commercial occupancy is either on an annual or 3 year inspection cycle. To be on an annual inspection cycle the occupancy:

A

Requires two or more exits

32
Q

passageways on roofs shall be provided for access around or through any approved structures or equipment installed on the roof. These passageways shall be at least ____ feet wide and have at least _____ feet in overhead clearance.

A

3 ; 7

33
Q

smoke detectors required by Ch 9 of the Building Code in apartments and hotels must be tested and documented every:

A

6 months

34
Q

if an apartment house has ____ or more dwelling units or a hotel has ___ or more guest rooms, either an owner or responsible resident shall reside on the premises.

A

16, 20

35
Q

in a basic commercial occupancy in no case shall the clearance between the bottom of a portable fire extinguisher and the floor be less than:

A

4 inches