auc 338 application of water on energized electrical equip. Flashcards

0
Q

Can you apply water with tan lines on the energized or grounded electrical equipment?

A

The procedure is as outlined in this bulletin pertain to all electrical equipment whether it is energized, D energized, or grounded

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
1
Q

Can first responding units use hand lines on energized electrical components at con Ed facilities?

A

Hanline’s shall never be used on energized electrical components at con Edison facilities

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

If you were on scene at a con Edison facility and a deputy chief asked you to apply a stream to electrical component may you do it?

A

The decision to apply water streams to electrical components at con Edison facilities will not be undertaken by first responding units.this decision can only be made by a chief officer above the rank of deputy or a deputy chief operating as car for 421 in consultation with the con Edison white hat at the scene

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Once the maximum voltage potential for the facility is known, safe operational distances must be determined based on the type of water stream to be used. what is the safe operating distance on live 138 KV electrical components for 30° or greater fog streams?

A

15 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the minimum safe operating distance on live 138 KV electrical components for all straight or solid streams and streams less than 30° fog?(29)

A

75 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the minimum safe operating distance on live 345 KV electrical components 30° or greater fog streams?

A

25 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the minimum safe operating distance on live 345 KV electrical components for all straight or solid streams and streams less than 30° fog?(29)

A

125 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the primary means of applying water to energized electrical components?

A

Tower ladder
Clear all sediment from the water supply by flushing the hydrants thoroughly before connecting to the pumper. The type of tip to be used on the tower ladder is dependent on the ability of the stream to reach the target area. Examples :stack tips to supply a solid stream and the akon turbo master nozzle which has been adjustable stream pattern from straight to fog position. The waterway of the tower ladder mustang be flushed away from the point of operation and all electrical components for several minutes until the water runs clear.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Is it okay to have members in the tower that a basket while applying streams to electrical components?

A

All members are removed from the basket in the basket is then raised to operating position. All members are then removed from the apparatus. The stream will then be applied to the target area.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

If the stream is not reaching the intended target area where do you shut down the water supply?

A

At the pumper. Then the position of the basket or angle shall be adjusted. Once the basket is repositioned, and all members are off the apparatus water is against applied to the tower ladder. Note: when the stream is repositioned, in sure that the minimum safe operating distance for the type of stream employed is maintained.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

If the tower ladder is no good can we consider engine deck gone, latter pipe, or the Akron New Yorker?

A

Yes. Aqua stream Master nozzles carried by all engine and ladder companies is factory preset to a fog at 130°. Don’t use this because it doesn’t allow enough stream penetration to allow for maintaining safe distances.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

If the shit is hitting the fan can we enter a con Ed facility without approval of con Ed white hat?

A

Entry of members or any apparatus with in con ed facility shall only be with approval of con Ed white hat with an escort. Follow directions of white hat while inside facilities. FDNY members shall never enter inside the con Edison facility property line unless escorted by qualified con Edison station personnel and with the approval of the incident commander

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

True or false
Confirm that all con ed equipment inside the con Ed property line is connected to the facilities station ground prior to applying water.

A

False
Confirm all FDNY equipment inside con Ed proper property line is connected to the facilities station ground prior to applying water. Con Edison personnel shall confirm this

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

True or false

Either freshwater or salt water can be used for apply water streams on live electrical components.

A

False.

Only freshwater shall be used for applying water streams on live electrical components. Saltwater shall never be used.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Is it safe to add foam while applying streams to electrical equipment?

A

No additives including any type of foam shall be used. Additives increase the electrical conductive any of the water.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Fog streams are poor conductors of electricity and are there for the preferred water stream pattern. The desired fog pattern mode is a ___or greater fog stream.

A

30° or greater

16
Q

Fog streams can greatly be affected by wind conditions and may not reach the target area from a distance of 15 or 25 feet. In these situations what do you do?

A

A straight stream utilizing the fog tip or a solid stream shall be used and the standoff distances is increased

17
Q

True or false

The possibility of runoff water from a con Edison facility being charged with electrical current is extremely likely.

A

False
Is extremely remote. All con Edison facilities have Station grounding mats installed that would absorb any stray electrical currents and prevent pools of water outside the facility from being charged. However, avoid low spots when positioning apparatus and appliances. Member should also avoid water runoff.

18
Q

True or false
FDNY dispatchers will not give a specific address for a con Edison generating facility to responding units, but will use a more generic term e.g. con Edison victory Boulevard

A

True
The battalion chief can choose a rendezvous muster site placement of identifying decal. The decal is a larger version of an official far department shoulder patch with a con Edison white helmet and FDNY chiefs helmet display there

19
Q

True or false
Some substations are architecturally designed to mimic surrounding buildings styles and may not be immediately recognizable as substations.

A

True

20
Q

If power has been removed, two capacitors retain a potentially deadly electric charge?

A

Yes

21
Q

True or false
Set up Hanline’s and/or large caliber streams to protect expose buildings around the substation. Do not direct water into the substation or put water on electrical equipment unless requested by the con Edison white hat.

A

True

22
Q

True or false

A 3 1/2” supply line shall be stretched and charged to the sprinkler Siamese if present.

A

False
A 3 1/2 inch supply line shall be stretched, but not charged, to the sprinkler Siamese if present. If requested by con Edison white hat, supply the Siamese with water at the posted pressure. Sprinklers if present protect only the Transformers.

23
Q

What type of extinguishing agent should we use at battery room fires?

A

Dry chemical extinguisher will work here as well as water application from a safe distance. Carbon dioxide should not be used as an extinguishing agent at these fires. The plastic battery shells make crack one called CO2 gas is applied to the fire.

24
Q

Inside substations can we cut fences or force open locked doors or gates?

A

No. Do not cut Fences or force open locked gates or doors. Inside substations, ground-level electrical hazards are Fenston or Behind locked doors and gates.

25
Q

Avoid bringing metal tools into substations and do not allow any tolls to project above your______.

A

Shoulder. Also, would or fiberglass hooks can conduct high-voltage is found in substations.
Note: always assume that water runoff and smoke is contaminated with PCBs. Operate uphill and upwind where possible.

26
Q

When raising aerial ladders and tower ladder buckets, maintain and _____foot safe clearance horizontally from the substations exterior fence line and do not place portable ladders, aerial ladders or tower ladder Booms or buckets against or over the wall or fence.

A

18 foot safe clearance horizontally

27
Q

True or false
Where full PPE to protect from potential dermal and respiratory hazards. S CBA’s shall be worn even in a light smoke condition due to the potential for PCB contamination.

A

False
SCbA’s shall be used even in the light smoke condition due to the potential for PCB contamination. Always operate as of PCBs are present. Consider decontamination when exposed to smoke, oil or possibly contaminated water runoff.

28
Q

All con Edison substations have been entered into the CIDS program. When independent substations are discovered should they be entered into the CIDS program?

A

Yes