What loads can be supplied by the Aux Boilers?
- SJAE
- OFG Preheaters
- CSRs
- HVH Aux HX
What loads can be supplied from Extraction Steam?
- CSRs
- HVH Intermediate HX
Why are the steam supply valves from MSS/ESS interlocked with ABS?
Prevents cross contamination of the Aux Boilers from MSS/ESS
What is the isolation valve for the MSS supply to ASS?
2ASS-MOV148
What Stage ESS supplies the CSRs?
9th Stage (4th Point) ESS
When will the CSR Steam Supply auto swap?
2ESS-STV104 will auto open when 4th pt pressure is >57#, It will auto close at <50# or on a Turbine Trip. 2ASS-STV112 is the valve that swaps with it, in addition, 2ASS-STV112 will also close if MSS pressure is <200#
When will a CSR Steam Admission Valve (MOV3’s) Auto Close?
- CSR level 4” below normal level
- Drain tank 14’ above normal level (Hi-Hi)
When does the CSR Steam Outlet valve(MOV16’s) Auto Close?
Closes on a CSR Hi-Hi level (8” above normal)
What will Lock Up the CSR Drain Tank Level Control Valves, LV8’s?
If Both MOV3A and MOV3B are open at the same time
When do the CSR Drain Tank dump valves(LV9’s) open?
CSR Drain Tank 10” above normal (Hi-Hi)
When do the CNA-LV8’s (CSR Drain Tk LVs) Auto Close?
- High level in 4th Pt FWS Htr
- Hi-Hi level in 1st or 2nd Pt FWS Htr
When will the HVH Intermediate steam admission valves (MOV8’s) Auto Close?
Intermediate HX Lvelv Hi-Hi (4” above Normal)
What will trip an Aux Boiler?
- Above 7” Water Level
- Above 157psig
- Ground Overcurrent