AS114 - Lecture - Troubleshooting Flashcards
broken circuit / incomplete path for current flow means its a ____ _____
Open circuit
Meter Indications on a Ohmmeter for an open circuit are:
Ohmmeter- RT will be infinite resistance
No needle movement on analog meter
OL on digital meter
location of open identified by showing infinite resistance across 2 point of circuit
all other resistance measurements will be normal
Meter Indications on a Voltmeter for an open circuit are:
Voltmeter- ET will show normal system voltage
location of open identified by showing system (source) voltage across 2 points of circuit
there will be no other voltage drops in the circuit
Meter Indications on a Ammeter for an open circuit are:
Ammeter- IT will be 0 amps (lower than normal in a parallel circuit)
More resistance than there should be in the circuit is a fault known as
Added Resistance-
Meter Indications on a Ohmmeter for added resistance read:
Ohmmeter- RT will be higher than normal
location of fault identified by showing higher resistance across 2 point of circuit (or resistance where there shouldn’t be any)
all other resistance measurements will be normal
Meter Indications on a Voltmeter for added resistance read:
Voltmeter- ET will show normal system voltage
location of fault identified by showing higher than normal voltage drop across 2 points of circuit
all other voltage drops in the circuit will be lower than normal.
Meter Indications on a Ammeter for added resistance read:
Ammeter- IT will be lower than normal
When the current bypasses all or part of the load is know as
Short Circuit ( two types are Partial and Dead)
When current is bypassing part of the electrical load
C/B or fuse may or may not pop
it is known as
Partial Short
Meter Indications on a Ohmmeter for Partial Short Circuit read:
Ohmmeter- RT will be lower than normal
location of fault identified by showing no resistance (0 Ω) across 2 point of circuit
all other resistance measurements will be normal
Meter Indications on a Voltmeter for Partial Short Circuit read:
Voltmeter- ET will show normal system voltage
location of fault identified by showing no voltage drop (0 v) across 2 points of circuit
all other voltage drops in the circuit will be higher than normal.
Meter Indications on a Ammeter for Partial Short Circuit read:
Ammeter- IT will be higher than normal
When the current is bypassing all of the electrical load
C/B or fuse will pop it is a:
Short Circuit