3.8.4 DC Sources Operating:
The train A and Train B DC electrical power subsystems shall be OPERABLE
Applicability: ??
Modes 1, 2, 3, and 4
3.8.4
A. One battery charger on one subsystem inoperable
A.1 Restore battery terminal voltage to greater than or equal to the minimum established float voltage (2 hours)
AND
A.2 Verify current battery float voltage <2 amps (once per 12 hours)
AND
A.3 Restore battery charger to OPERABLE status (72 hours)
3.8.4
B. One DC electrical power subsystem inoperable for reasons other than condition A
B.1 Restore DC electrical power subsystem to OPERABLE status
(2 hours)
3.8.4
C. Required action and associated completion time not met
C.1 Be in mode 3 (6 hours)
AND
C.2 be in mode 5 (36 hours)
3.8.4
Each DC electrical power subsystem consists of _________.
Two 125VDC batteries, the associated battery charger(s) for each battery, and all associated control equipment and interconnecting cabling.
3.8.4
The battery cells nominal specific gravity is ____.
1.215 +/- 0.010