060201abB Drainage And venting systems :Part B Flashcards

1
Q

Minimum fixtures required for installation in a single-family dwelling 

A

Kitchen sink, water closet, lavatory, bathtub/ shower , laundry standpipe, floor drain

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Requirements for laundry standpipe

A

Must be a minimum 24” above trap weir

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Max distance for 1 1/4” trap

A

5ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Max distance for 1 1/2” trap

A

6ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Max distance for 2” trap

A

8 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Max distance for 3” trap

A

12ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Max distance for 4” trap

A

32ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When does a wet vent start and end

A

Starts from the trap arm connection from the most upstream fixture to the last fixture connection on the vertical pipe with the water closet being the most downstream connection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Max water closets on a wet vent

A

Two

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Required flashing size

A

20x20” minimum

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What’s the amount of contact a flashing needs to make

A

4” minimum

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What’s the minimum requirements for a Type A (flat) roof flashing

A

Minimum height 6” above roof

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Water closet maximum trap arm

A

1 metre vertically and 3 metres horizontally

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Can dis similiar fixtures be dual vented

A

Yes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When does a flat vent be sized as a stack vent rather than a individual vent

A

If the drainage piping serving the above fixtures passes through more than one story

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What table is used for wet vent sizing

A

2.5.8.1

17
Q

What’s the max number of wet vented water closets

A

Two

18
Q

All trap arms and fixture drains connected to the wet vent do not exceed what size

A

2”

19
Q

Where a wet vent extends through more than one storey the total discharge from any one storey above the first storey does not exceed how many fixture units

A

4

20
Q

A soil or waste pipe can serve as a wet vent provided there is not more than one nominally horizontal offset in the wet vent and does not exceed what distance

A

1.2m or 4 ft for 2”
2.5m or 8 ft for above 2”

21
Q

What fixture units are not considered when sizing a wet vent

A

The most downstream fixture as it’s not draining through the wet vent portion

22
Q

T OR F- there is no limit to the maximum length of a wet vent, the concern is the maximum distance from the trap to the vent

A

True

23
Q

What table takes precedence over all other venting tables

A

Table 2.5.7.1

24
Q

In cases of vent stacks exiting the roof where there is occupancy how far must the vent be

A

3.5

25
Q

Vent pipes can’t terminate out of the roof any shorter than

A

6”