060201abA Drainage And Venting Systems: Part A Flashcards
What is the limit of directional change in the trap arm before the fixtures vent must be connected
135 degrees
What is the maximum a trap arm fall/ grade before it connects to a vent
Cannot drop larger than it’s inside diameter- ex 1 1/2” pipe cannot drop/ grade more than 1 1/2” ( 6ft with 1/4” per ft)
What is the minimum length of a trap arm?
Double the pipe diameter
What special allowance for trap arms are water closets given
Extra 90 degrees of change for 225 degrees
How much change vertically and horizontally do water closets get
1 metre vertically
3 metres horizontally
What spots are clean out mandatory
-where the building drain enters a building
-the base of every stack
-directly above every running trap
-in a location permitting the cleaning of any interceptor
Where can a Tee wye be used
Only used for vents or vertically on a drain where it connects to a vent
What fitting can’t be used for connection of two back outlet water closets in a back-to-back installation
Double tee wye
Is a double tee wye permitted with back to back or side to side lavs ?
Yes
If you use a double tee wye to connect two urinals where does the clean out go ?
Ontop
A horizontal drainage pipe must not have a wye taken off how far from a vertical stack if that stack receives 30 or more fixture units or receives sewage from 2 or more stories above
1.5m
What size floor drains are considered emergency fixtures
3” or bigger
How far can a 3” floor drain run before a vent connection
12 feet at 1/4 inch per foot
Minimum trap arm for an un-vented floor drain
18”
What type of backwater valve is not allowed
A Normally closed valve (N/C )