WS 5 Flashcards
Each station outlet/inlet for medical gas or vacuum shall be ____.
Gas-specific.
Each station outlet shall consist of a(n) ____ valve and a secondary valve (or assembly).
Primary.
Each station inlet shall consist of a primary valve (or assembly) and hall be permitted to include a(n) _____ valve (or assembly)
Secondary.
Station outlets in systems having nonstandard operating pressures shall be ____ where a single gas is piped at more than one operating pressure.
Pressure-specific.
Station outlets that operate at a pressure in excess of ____ shall be either D.I.S.S. or be designed to relieve pressure prior to removal of the adaptor.
80 psi.
Station inlets for WAGD service shall not be ____ with any other systems.
Interchangeable.
The standing pressure test for manufactured assemblies shall be permitted to use any testing method that will ensure a pressure decay of less than ____.
1% in 24 hours.
Manufactured assemblies employing flexible hose shall use hose and flexible connectors with a minimum burst gauge pressure of ____.
1,000 psi.
Manufactured assemblies shall have a flame spread index of no greater than ____ when tested in accordance with ASTM E 84.
200.
Station outlet/inlets of manufactured assemblies that employ flexible hose or flexible connectors to the piping system, that are not fully and immediately accessible, shall use ___ connectors.
D.I.S.S.
MGR assemblies shall be made of materials with a melting point of at least ____.
1,000 degrees F.
The scale range or positive pressure analog indicators shall be such that the normal operating pressure is within the ____ of the total range.
Middle third.
The accuracy of the digital indicators shall be +-_____ percent of the operating pressure at which they are used.
5.
The scale range of vacuum indicators shall be ____ gauge HgV.
0-30”
The rated accuracy of pressure indicators used for testing shall be ____ percent (full scale) or better at the point of reading.
1%