Category 1 medical-surgical vacuum sources shall, at a minimum, consist of _____ or more vacuum pumps.
Two
Category 1 medical-surgical vacuum sources shall consist an automatic means to prevent _____ through any off-cycle vacuum pump.
Backflow
Piping between the vacuum pump(s), discharge(s), receiver(s), and the source shutoff valve, shall be permitted to be brass, galvanized, or black steel pipe. True or false?
True.
Vacuum receivers shall comply with _____ “Unfired Pressure Vessels” of the ASME Boiler and Pressure Vessel Code.
Section VIII
Vacuum receivers shall be capable of withstanding a gauge pressure of ____ psi and _____ gauge HgV.
60; 30
The medical-surgical vacuum receiver shall be Max’s serviceable without shutting down the system by _____.
Any method to ensure continuation of service.
When the medical-surgical vacuum pump(s) in operation is (are) incapable of adequately maintaining the required vacuum, additional pumps shall be _____ activated.
Automatically.
Each pump motor shall be provided with an automatic restart function such that the pump(s) will restart after the power interruption without manual intervention. True or false?
True.
The medical-surgical vacuum pumps shall exhaust in such a manner and location that ____ the hazards of the noise and contamination.
Minimizes.
Medical vacuum exhaust can be located near places of public assembly as long as the end is turned down and screened. True or false?
False.
The medical-surgical vacuum exhaust shall be turned down and screened. The screening shall be fabricated using what type of material?
Any non-corroding material.
Multiple vacuum pumps shall be permitted to be joined together to one common exhaust, provided the common exhaust is sized to ____.
Minimize back pressure
Vacuum exhausts from multiple pumps joined together to one common exhaust, shall be permitted provided each pump can be isolated by _____.
Blind flange
Manual valve
Or check valve.
Category 1 medical-surgical vacuum systems shall activate which alarm, when the backup of lag pump is running?
Local.
What is not permitted to be used for the removal of waste anesthetic gas disposal (WAGD)?
An exhaust hose stuck out a window.