The quality of instrument air shall be ____.
Filtered to .01 micron,
Freed of liquids,
And feee of hydrocarbon vapors.
The quality of instrument air shall be dry to a dew point of ___.
-40 degrees F.
Instrument air systems shall be permitted to interconnect with medical air systems that have at least two or more compressors. True or false?
False.
Instrument air sources shall produce air at not less than a gauge pressure of ____.
200 psi.
Where instrument air systems are provided with a standby header, the header shall have how many cylinders attached?
One hour of normal operation.
Instrument air intake shall be permitted to be drawn from:
Outside air,
Ducted air,
And equipment room.
Instrument air sources shall be filtered with activated carbon filters and be located upstream or the final line filters. True or false?
True.
Final line filters for instrument air shall be rated for a minimum of ____ efficiency at ____ micron.
98%; .01
Final line filters for instrument air shall be equipped with a continuous visual indicator showing the status of the filter element life. True or false?
True.
What alarm shall the instrument air activate to indicate when or just before the backup compressor (if provided) is in operation?
Local.
Instrument air systems shall activate the alarm systems when the dew point at system pressure exceeds _____.
-22 degrees F
Instrument air sources with standby headers shall activate an alarm at the compressor site, a local signal at the header location and all master panels. True or false?
True.
Instrument air sources with standby headers shall be alarmed to indicate ____.
Reserve in use,
High dew point,
And reserve low.
All valves except zone valve box assemblies shall be ____.
In a secure area,
Locked or latched in their operating position, and
Labeled appropriately.
With the approval of the authority authority having jurisdiction, in what areas shall shutoff valves be permitted to be secured to prevent inappropriate access?
Psychiatric or pediatric.