Medical air sources shall be used only for
Human respiratory applications.
Medical air compressor systems shall have a(n) ____ means to prevent back flow through all off-cycle compressors.
Automatic.
Medical air compressor systems shall have a pressure relief valve set at ___ percent above line pressure.
50%
Liquid ring and permanently sealed bearing compressors shall separate the oil-containing section from the compression chamber by at least two seals. True or false?
False.
For liquid ring compressors, service water and seal water shall be treated to control _____.
Waterborne pathogens
Chlorine
And hyper chlorination
Aftercoolers, where required, shall be provided with individual _____.
Condensate traps.
Receivers for medical air shall be equipped with ____.
Relief valves
Automatic manual drains
And sight glass
Medical air filters shall be located immediately upstream of the ____.
Final line regulator.
Medical air filters shall be sized for 100 percent of the system peak calculated demand, and be rated for a minimum of ____ % efficiency at ____ micron or greater.
98%; 1
Medical air compressors shall be sufficient to serve the peak calculated demand, with the largest single compressor out of service. In no case shall there be fewer than ____ compressors.
2
Medical air receivers shall be provided with proper valves that allow the receiver to be ____.
Bypassed.
Dryers, filters, and regulators shall be at least duplexed. Under normal operation, airflow shall be divided by equally through each device. True or false?
False.
Medical air shall be sampled at a ____ NPS valves sample port down stream of the final line pressure regulator.
1/4”
Where medical air piping systems at different operating pressures are required, the piping shall separate after the ____.
Filters.
Medical air compressors shall be provided with a(n) ____ restart function, such that the compressors will be restarted after a power interruption.
Automatic.