Wet Vent Flashcards

1
Q

All fixtures in a wet vented group must be located in the same floor level

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The highest fixture of a wet vented group must be connected to a…

A

Continuous waste vent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When two water closets are wet vented how are they to be connected?

A

Independently to the vertical portion of the stack using a double outlet fitting in conformant with table 7.2.4.5

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

The maximum number of fixtures in a wet vented group is

A

Unlimited

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The minimum size wet vent serving a water closet is

A

2 inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The minimum size wet vent for a 4 inch drain is

A

2 inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The maximum fixture units that may discharge into a wet van from one story above the low story of a wet vented group is

A

4 fixture units

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When a stack serving as a wet vent is more than four stories high

A

The stock must extend full-size independently to open air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The maximum horizontal offset of a 2 inch wet vent is

A

1200 mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

The maximum horizontal offset of a 6 inch wet vent is

A

2500 mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the maximum size of fixture drain that may be connected to a 2 inch wet vent above the connection of white vented water closet?

A

2 inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

A 3 inch floor or hub drain may be connected to a wet vent provided

A

The trap arm is at least 450mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How many fixture units may discharge into 1 1/2” wet vent serving a water closet?

A

0

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When determining the size of a wet vent, the fixture unit load of individually vented fixtures connected to the wet vent or the trap arm of a wet vented. Water closet are not taken into consideration.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When determining the size of a wet vent, the fixture unit load of the water closet, or lowest connection fixture is not taken into consideration

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When determining the size of a continuous vent, the fixture unit load of individually vented fixtures connected to the wet vent, or the trap arm of a wet vented, water, closet, or not taken into consideration

A

True, true