Offset Relief Vents Flashcards

1
Q

An offset relief vent is not required when the horizontal offset in the stack is

A

1500 mm or less

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The recommended connection height of an offset relief vent to the vent stack is

A

1000 mm above finished floor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

In An offset relief vent installation, where is the upstream relief fan connected to the stack

A

To the upper vertical section of the stack immediately above the offset

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

In an offset relief vent installation, where is the downstream, relief and connected to the stack

A

Any of the above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The size of an offset relief fence, serving a 6 inch soil stack would be

A

2 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The number of stories, the upper vertical section of a stack needs pass through in order to require an offset relief vent is

A

More than two stories

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Horizontal offset in a 4 inch foil stack has is 2000 mm in length, the upper vertical section of the stack is five stories, high and receives a discharge of 145 FUs. Does this offset require an offset and if so what would be the minimum size

A

Yes, 1 1/2”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How many fixtures are permitted to be discharged into an offset relief vent?

A

2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly