Wet and Dry Pipe Valves Flashcards
Vane type flow paddle will not operate ______
Water motor gong
Audible alarm must be heard within
5 minutes
Piping between the sprinkler system and pressure actuated alarm initiating device shall be
Non corrosive pipe, no smaller then 3/8”
Alarm line is to be auto drained through
A restricted orfice
Drain pipe on alarm line to be no smaller than
1/4”
Paddle type water flow alarm indicators shall be installed in _____
Wet systems only
PS10 switch is
Alarm switch, can be used on any system
PS120 is
Supervisory, low water pressure
Generally used on wet systems
PS40 is
Supervisory, Low air
Generally used on dry systems
The 3 different kinds of seating arrangements for alarm valves are
Split/Groove
Pilot Port
Divided ring
Which seating arrangement has grooved rings with a large channel for feeding alarm line
Split/Groove
Which seating arrangement has a separate clapper and larger opening to the alarm line that is prone to issues
Pilot Port
Which seating arrangement has 2 separate rings with small holes between the seats
Divided ring
Water motor gongs need
Constant water supply to operate
Piping for water motor going can not be less than
3/4”
Maximum vertical distance WMG can be from alarm valve is
20’
Maximum horizontal distance WMG can be from alarm valve is
75’
Excess pressure pumps must be
Hardwired
Excess pressure pumps can either be
Manual or automatic
A retard chamber takes ______
Small surges from city supplies and discharges them to the drain
Where does a retard chamber generally vent though
Water motor gong pipe