Standard Spray Sprinklers Flashcards
Predetermined testing bodies for sprinkler heads are
UL, ULC, FM
Thread sizes for sprinkler heads are
1/2”, 3/4, 1”
What is the sprinkler orfice held close with
Cap/plug that is secured by fusible element, tensioned with screw in deflector
What determines K factor
Orfice size
How much psi is required to create proper spray pattern
7psi
How many gpm is required to create proper spray pattern
15gpm
What is the standard spray k factor
5.6
K factor is
The amount of water that will flow through the orfice with 1 pound of pressure
What is the formula for figuring out the K factor, GPM, or PSI
Q
———
K | √P
How much water is directed downwards from sprinkler discharge
100%
What sprinkler must meet the minimum flow requirements?
The furtherest sprinkler from the fire pump/incoming
How sprinklers must be permanently marked with
-1-2 letters which indicate manufacturer
-3-4 numbers which indicate k factor, deflector characteristics, pressure rating, thermal sensitivity
Fusible element temp is selected based on
Ceiling temp
Why does a frangible bulb burst when heated
The liquid expands, compresses the air bubble, continues until glass breaks
What are solder link heads mostly constructed of
Alloy with pre determined melting points
Standard response response time index is
> 80 (greater than 80)
Fast response sprinklers response time index is
<50 less than
Response time index is calculated
(Meters-Second) 1/2
How must frame of upright be installed
Parallel to branch line piping to minimize obstruction
When must protective caps be removed
Right after install
Sprinklers subject to mechanical damage must be protected with
Listed guards
Available corrosive resistant coating include
Brass, chrome, polyester, PTFE, Wax, ENT, stainless
Who can paint heads
Only manufacturer
Head box shall contain what in addition to sprinklers
Paper with sprinkler identification number, or manufacturer, model, orfice, deflector type, thermal sensitivity, pressure rating
How many heads in head box on a site with less then 300 heads
6
How many heads in a head box on a site with 300-1000 heads
12
How many heads in a head box on a site with >1000 heads
24
Where can standard spray upright and pendants be installed
-all hazard classification types
-Quick response must be installed in light hazard
-Quick response not permitted to be installed in Extra hazard
Standard spray sidewalls can be used
Light & ordinary hazard with smooth, slopped, or flat ceilings
Not permitted in extra hazard
Below overhead doors
Max coverage area and max space for upright/pendant in light hazard
225ft2 and 15 feet
Max coverage area and max space for upright/pendant in ordinary hazard
130ft2 and 15’
Max coverage area and max space for upright/pendant in extra hazard
100ft2 and 12’
What’s the minimum distance from walls sprinkler heads need to be
4”
Small room only applies if
It’s light hazard
Unobstructed construction
800sq ft max
9’ max from one wall
Cannot exceed max coverage
3 types of sprinkler obstructions are
-To sprinkler discharge
-Spray pattern development
-To reach hazard
Additional protection is required below obstructions greater then
4 feet
Standard spray side wall max coverage and max space in light hazard
196sq ft and 14’
Standard spray side wall max coverage and max space in ordinary hazard
100 sq ft and 10’
NFPA 13R is
Standard for sprinklers in buildings no more then 4 stories and no higher then 60’
NFPA 13D is the standard for
Dwellings/homes
Where are quick response sprinklers permitted with NFPA 13R
In compartments and where no more then 4 sprinklers are in a unit
What’s the minimum density within a compartment NFPA 13R
0.10/ft squared
How are non residential heads installed in NFPA 13R and 13D
In accordance with NFPA 13
Where are quick response heads permitted in NFPA 13D
Closets, saunas, steam rooms
Residential sprinklers can only be used on
Wet systems only
Residential sprinklers must be how far from Ceiling
1-4”
Bathrooms under how big do not need sprinklers
55sq feet and under
Closets cannot exceed what size
24ft sq
Water delivery time for residential
15 seconds
If a dry system is installed per NFPA 13R, what heads are to be used
Standard spray
Minimum drain for NFPA 13R is
1” plus 1/2” Auxiliary drain on dry systems that may freeze if needed
NFPA 13D minimum size drain is
1/2”
How is pipe pitched to drain in NFPA 13D
1/4” per 10’
What is not required on NFPA 13D?
Fire department connection
FDC is required in NFPA 13R if
The building exceeds 2000ft sq or more then one storey
Minimum size for the FDC NFPA 13R
1-1/2”
NFPA 13R, more then 20 heads, what is the testing procedure
Hydro test for 200psi for 2 hours
NFPA 13R where there is less then 20 heads how must testing be done
50 psi over normal system pressure
Small room rule only applies in rooms
800 sq ft and less
How far below ceilings can an standard spray upright be? (unobstructed)
1-12”
How far below ceilings can an standard spray upright be? (obstructed)
1-6” below structural member, no more then 22” from ceiling
What is the clearance to storage for standard spray uprights and pendants
18”
What is the minimum distance between standard spray uprights and pendants
6 feet
What is the distance below ceilings for a standard spray side wall
4-6”
How far must standard spray sidewalls be apart
6 feet
Max ceiling temp for ordinary head
100F
Max ceiling temp for intermediate head
150F
Max ceiling temp for high head
225F
Max ceiling temp for extra high head
300F
Temp rating for ordinary heads
135-170F
Temp rating for intermediate heads
175-225F
Temp rating for high heads
250-300F
Temp rating for extra high heads
325-375F
Colour code for ordinary head
Uncoloured or black
Colour code for intermediate head
White
Colour code for high head
Blue
Colour code for extra high head
Red
Glass bulb colour ordinary head
Red or orange
Glass bulb colour intermediate head
Green or yellow
Glass bulb colour high head
Blue
Glass bulb colour extra high head
Purple
Where can hi temp heads be used
Ordinary and extra hazard
When installing upright sprinklers on a 6” main, what is the minimum length the candle can be
18”
Ceiling pockets in NFPA 13R and D cannot exceed
100ft cubed
Ceiling pocket in NFPA 13R and D cannot exceed _____ in depth
12”
Ceiling pocket in NFPA 13 cannot exceed
1000ft cubed
Ceiling pocket in NFPA 13 cannot exceed ____ in depth
36”