Deluge & Pre-Action Valves Flashcards
How is the operation of a deluge valve controlled
By release of water in the priming chamber
3 styles of detection lines that we can utilize for deluge and pre action valves are
- Hydraulic
- Pneumatic
3.Electric
What allows the seat to remain closed
Differential force generated within the deluge valve priming chamber
The differential is typically designed to produce _____ as much force in the priming chamber as the supply water pushing against
Twice
Pressure relief can be omitted for single interlock when
The air supply is not capable of developing more then 15psi
Max size single interlock
1000 heads
Max size non interlock
1000 heads
Max size double interlock
500 gallons
Which interlock system cannot be gridded
Double interlock
Air leakage “maintenance” test consists of
40 psi for 2 hours, 3 psi max loss
Class A- ordinary combustibles- symbol and colour
Green triangle
Class B - Flammable liquids- symbol and colour
Red square
Class C - live electrical- symbol and colour
Blue circle
Class D - Flammable metals- symbol and colour
Yellow star
Class K- Kitchen components- symbol and colour
Black octagon