Understanding NEC Articles 242 & 300 Flashcards
Article _____ provides the general requirements installation requirements and connection requirements for overvoltage protection and overvoltage protective devices.
Answer 1: 242
Answer 2: 285
Answer 3: 286
Answer 4: 287
Answer 1: 242
242.1
Surge-protective devices shall be _____.
Answer 1: listed
Answer 2: identified
Answer 3: marked
Answer 4: labeled
Answer 1: listed
242.6
A surge-protective device shall not be installed in circuits over _____.
Answer 1: 480V
Answer 2: 600V
Answer 3: 1000V
Answer 4: 4160V
Answer 3: 1000V
242.12(1)
Type 1 SPDs shall be permitted to be connected on the supply side of the _____ disconnect.
Answer 1: service
Answer 2: feeder
Answer 3: branch-circuit
Answer 4: outside feeder
Answer 1: service
242.13(A)(1)
A _____ surge-protective device is permitted to be connected on either the line or load side of a service disconnect overcurrent device.
Answer 1: Type 1
Answer 2: Type 2
Answer 3: Type 3
Answer 4: Type 4
Answer 1: Type 1
242.13(A)
Type 2 SPDs shall be connected at the building or structure anywhere on the load side of the _____.
Answer 1: first overcurrent device
Answer 2: service attachment point
Answer 3: meter socket
Answer 4: transformer
Answer 1: first overcurrent device
242.14(B)
The conductors used to connect the surge-protective device to the line or bus and to ground shall not be any longer than _____ and shall avoid unnecessary bends.
Answer 1: 6 in.
Answer 2: 12 in.
Answer 3: 18 in.
Answer 4: necessary
Answer 4: necessary
242.24
Conductors for ac and dc circuits under 1000V ac and 1500V dc can occupy the same _____ provided that all conductors have an insulation rating equal to the maximum voltage applied to any conductor.
Answer 1: equipment wiring enclosure
Answer 2: cable
Answer 3: raceway
Answer 4: any of these
Answer 4: any of these
300.3(C)(1)
The requirement to run all paralleled circuit conductors within the same _____ applies separately to each portion of the paralleled installation.
Answer 1: raceway or auxiliary gutter
Answer 2: cable tray or trench
Answer 3: cable or cord
Answer 4: all of these
Answer 4: all of these
300.3(B)(1)
Conductors installed in nonmetallic raceways run underground shall be permitted to be arranged as isolated _____ installations. The raceways shall be installed in close proximity and the conductors shall comply with 300.20(B).
Answer 1: neutral
Answer 2: grounded conductor
Answer 3: phase
Answer 4: all of these
Answer 4: all of these
300.3(B)(1) Ex
Where a cable or raceway-type wiring method is installed through bored holes in joists rafters or wood members the holes shall be bored so that the edge of the hole is _____ the edges of the wood member.
Answer 1: not less than 1¼ in. from
Answer 2: immediately adjacent to
Answer 3: not less than 1⁄16 in.
Answer 4: 90° away from
Answer 1: not less than 1¼ in. from
300.4(A)(1) and Ex 1
Cables laid in wood notches require protection against nails or screws by using a steel plate at least _____ thick installed before the building finish is applied.
Answer 1: 1⁄16 in.
Answer 2: 1⁄8 in.
Answer 3: ¼ in.
Answer 4: ½ in.
Answer 1: 1⁄16 in.
300.4(A)(2)
Where Type NM cables pass through cut or drilled slots or holes in metal members the cable shall be protected by _____ which are installed in the opening prior to the installation of the cable and which securely cover all metal edges.
Answer 1: anti-short devices
Answer 2: sleeves
Answer 3: plates
Answer 4: listed bushings or grommets
Answer 4: listed bushings or grommets
300.4(B)(1)
Where nails or screws are likely to penetrate nonmetallic-sheathed cable or ENT installed through metal framing members a steel sleeve steel plate or steel clip not less than _____ in thickness shall be used to protect the cable or tubing.
Answer 1: 1⁄16 in.
Answer 2: 1⁄8 in.
Answer 3: ½ in.
Answer 4: ¾ in.
Answer 1: 1⁄16 in.
300.4(B)(2)
Where cables and nonmetallic raceways are installed parallel to framing members the nearest outside surface of the cable or raceway shall be _____ the nearest edge of the framing member where nails or screws are likely to penetrate.
Answer 1: not less than 1¼ in. from
Answer 2: immediately adjacent to
Answer 3: not less than 1⁄16 in. from
Answer 4: 90 degrees away from
Answer 1: not less than 1¼ in. from
300.4(D)
A cable raceway or box installed under metal-corrugated sheet roof decking shall be supported so the top of the cable raceway or box is not less than _____ from the lowest surface of the roof decking to the top of the cable raceway or box.
Answer 1: ½ in.
Answer 2: 1 in.
Answer 3: 1½ in.
Answer 4: 2 in.
Answer 3: 1½ in.
300.4(E)
When installed under metal-corrugated sheet roof decking _____ and intermediate metal conduit with listed steel or malleable iron fittings and boxes shall not be required to comply with 300.4(E).
Answer 1: rigid metal conduit
Answer 2: electrical metallic tubing
Answer 3: Schedule 80 PVC
Answer 4: all of these
Answer 1: rigid metal conduit
300.4(E) Ex 1
Conduit bushings installed to protect insulated conductors _____ or larger contained within raceways that are constructed wholly of insulating material shall not be used to secure a fitting or raceway.
Answer 1: 4 AWG
Answer 2: 6 AWG
Answer 3: 8 AWG
Answer 4: 10 AWG
Answer 1: 4 AWG
300.4(G)
Where raceways contain 4 AWG or larger insulated circuit conductors and these conductors enter a cabinet a box an enclosure or a raceway the conductors shall be protected from abrasion during and after installation by an identified fitting providing a smoothly rounded _____ surface.
Answer 1: fiberglass
Answer 2: plastic
Answer 3: insulating
Answer 4: gray
Answer 3: insulating
300.4(G)(1)
Electrical metallic tubing that is directly buried under a two-family dwelling driveway shall have at least _____ of cover.
Answer 1: 6 in.
Answer 2: 12 in.
Answer 3: 18 in.
Answer 4: 24 in.
Answer 3: 18 in.
300.5(A) Table Column 2
Rigid metal conduit that is directly buried outdoors shall have at least _____ of cover.
Answer 1: 6 in.
Answer 2: 12 in.
Answer 3: 18 in.
Answer 4: 24 in.
Answer 1: 6 in.
300.5(A) Table Column 2
A PVC raceway covered in 2 in. of concrete is required to have a minimal buried depth of _____.
Answer 1: 6 in.
Answer 2: 18 in.
Answer 3: 12 in.
Answer 4: 24 in.
Answer 3: 12 in.
300.5(A) Table Column 3
The minimum cover requirement for Type UF cable that supplies a 120V 15A GFCI-protected circuit under a driveway of a one-family dwelling is _____.
Answer 1: 6 in.
Answer 2: 12 in.
Answer 3: 16 in.
Answer 4: 24 in.
Answer 2: 12 in.
300.5(A) Table Column 4
For a dwelling location direct buried cables that are GFCI protected at no more than 20A shall have a cover of _____.
Answer 1: 6 in.
Answer 2: 12 in.
Answer 3: 18 in.
Answer 4: 24 in.
Answer 2: 12 in.
300.5(A) Table Column 4