Understanding NEC Article 230 Flashcards
The Code does not cover installations under the exclusive control of an electric utility such as _____.
Answer 1 service drops or service laterals
Answer 2 electric utility office buildings
Answer 3 electric utility warehouses
Answer 4 electric utility garages
Answer 1 service drops or service laterals
90.2(D)(5)(a)
A service drop is defined as the overhead conductors between the serving utility and the _____.
Answer 1 service equipment
Answer 2 service point
Answer 3 grounding electrode conductor
Answer 4 equipment grounding conductor
Answer 2 service point
100 Service Drop
The underground conductors between the utility electric supply system and the service point are known as the _____.
Answer 1 utility service
Answer 2 service lateral
Answer 3 service drop
Answer 4 main service conductors
Answer 2 service lateral
100 Service Lateral
The _____ is the point of connection between the facilities of the serving utility and the premises wiring.
Answer 1 service entrance
Answer 2 service point
Answer 3 overcurrent protection
Answer 4 beginning of the wiring system
Answer 2 service point
100 Service Point
Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads the conductor ampacity shall be no less than the noncontinuous load plus _____ of the continuous load.
Answer 1 80 percent
Answer 2 100 percent
Answer 3 125 percent
Answer 4 150 percent
Answer 3 125 percent
215.2(A)(1)
Feeder grounded conductors not connected to an overcurrent device can be sized at _____ of the continuous and noncontinuous load.
Answer 1 80 percent
Answer 2 100 percent
Answer 3 125 percent
Answer 4 150 percent
Answer 2 100 percent
215.2(A)(1) Ex 3
Service conductors and equipment for control and protection of services not over 1000V ac or 1500V dc nominal and their installation requirements are covered in Article _____.
Answer 1 210
Answer 2 220
Answer 3 230
Answer 4 240
Answer 3 230
230.1
If necessary to meet capacity requirements additional services are permitted for a single building or other structure by _____.
Answer 1 the registered design professional
Answer 2 special permission
Answer 3 the engineer of record
Answer 4 master electricians
Answer 2 special permission
230.2(C)(3)
Additional services are permitted for different voltages frequencies or phases or for different uses such as for _____.
Answer 1 gymnasiums
Answer 2 different rate schedules
Answer 3 flea markets
Answer 4 special entertainment events
Answer 2 different rate schedules
230.2(D)
Where a building or structure is supplied by more than _____ a permanent plaque or directory shall be installed at each service disconnect location denoting all other services supplying that building or structure and the area served by each.
Answer 1 one service
Answer 2 two services
Answer 3 three services
Answer 4 six services
Answer 1 one service
230.2(E)
Service conductors supplying a building or other structure shall not _____ another building or other structure.
Answer 1 be installed on the exterior walls of
Answer 2 pass through the interior of
Answer 3 be installed underneath
Answer 4 span the roof of
Answer 2 pass through the interior of
230.3
Service conductors shall be considered outside of a building or other structure where installed under not less than _____ of concrete beneath a building or other structure.
Answer 1 2 in.
Answer 2 4 in.
Answer 3 5 in.
Answer 4 6 in.
Answer 1 2 in.
230.6(1)
Circuit conductors other than service conductors shall not be installed in the same _____ as the service conductors.
Answer 1 raceway or cable
Answer 2 handhole enclosure
Answer 3 underground box
Answer 4 all of these
Answer 4 all of these
230.7
Where a service _____ enters a building or structure it shall be sealed in accordance with 300.5(G) and 300.7(A).
Answer 1 raceway
Answer 2 cable assembly
Answer 3 cable tray
Answer 4 any of these
Answer 1 raceway
230.8
Service conductors installed as unjacketed multiconductor cable shall have a minimum clearance of _____ from windows that are designed to be opened doors porches balconies ladders stairs fire escapes or similar locations.
Answer 1 3 ft
Answer 2 4 ft
Answer 3 6 ft
Answer 4 10 ft
Answer 1 3 ft
230.9(A)
The vertical clearance of final spans of overhead service conductors above or within _____ measured horizontally of platforms projections or surfaces that will permit personal contact shall be maintained.
Answer 1 3 ft
Answer 2 4 ft
Answer 3 5 ft
Answer 4 6 ft
Answer 1 3 ft
230.9(B)
Overhead service conductors shall not be installed beneath openings through which materials may be moved such as openings in farm and commercial buildings and shall not be installed where they obstruct _____ these building openings.
Answer 1 entrance to
Answer 2 egress from
Answer 3 access to
Answer 4 a safe descent from
Answer 1 entrance to
230.9(C)
Vegetation such as _____ shall not be used for support of overhead service conductors or service equipment.
Answer 1 shrubs
Answer 2 trees
Answer 3 potted plants
Answer 4 all of these
Answer 2 trees
230.10
Service-drop conductors shall have _____.
Answer 1 sufficient ampacity to carry the load
Answer 2 adequate mechanical strength
Answer 3 sufficient ampacity to carry the load or adequate mechanical strength
Answer 4 sufficient ampacity to carry the load and adequate mechanical strength
Answer 4 sufficient ampacity to carry the load and adequate mechanical strength
230.23(A)
The minimum size service-drop conductor permitted is _____ copper or _____ aluminum or copper-clad aluminum.
Answer 1 8 AWG 8 AWG
Answer 2 8 AWG 6 AWG
Answer 3 6 AWG 8 AWG
Answer 4 6 AWG 6 AWG
Answer 2 8 AWG 6 AWG
230.23(B)
Overhead service conductors installed over roofs shall have a vertical clearance of not less than _____ above the roof surface.
Answer 1 3 ft
Answer 2 4 ft
Answer 3 5 ft
Answer 4 8 ft 6 in.
Answer 4 8 ft 6 in.
230.24(A)
Where the voltage between conductors does not exceed 300 and the roof has a slope of 4 in. in 12 in. or greater a reduction in clearance to _____ over the roof is permitted.
Answer 1 3 ft
Answer 2 4 ft
Answer 3 5 ft
Answer 4 8 ft
Answer 1 3 ft
230.24(A) Ex 2
Where the voltage between conductors does not exceed 300 a reduction in clearance above only the overhanging portion of the roof to not less than _____ shall be permitted if not more than 6 ft of overhead service conductors pass above the roof overhang 4 ft horizontally.
Answer 1 12 in.
Answer 2 18 in.
Answer 3 2 ft
Answer 4 5 ft
Answer 2 18 in.
230.24(A) Ex 3
The requirement to maintain a 3-foot vertical clearance from the edge of a roof does not apply to the final conductor span where the service drop is attached to _____.
Answer 1 a service pole
Answer 2 the side of a building
Answer 3 an antenna
Answer 4 the base of a building
Answer 2 the side of a building
230.24(A) Ex 4