Understanding NEC Article 240 Flashcards
The next higher standard rating overcurrent device above the ampacity of the ungrounded conductors being protected is permitted to be used provided the _____.
Answer 1: conductors being protected are not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads
Answer 2: ampacity of the conductors does not correspond with the standard ampere rating of a fuse or circuit breaker
Answer 3: next higher standard rating does not exceed 800A
Answer 4: all of these
Answer 4: all of these
240.4(B)(1), (2), and (3)
If the circuit’s overcurrent device exceeds _____ the conductor ampacity shall have a rating not less than the rating of the overcurrent device.
Answer 1: 800A
Answer 2: 1000A
Answer 3: 1200A
Answer 4: 2000A
Answer 1: 800A
240.4(C)
Fixture wire is permitted to be tapped to the branch-circuit conductor in accordance with which of the following?
Answer 1: 15A or 20A circuits - 18 AWG up to 50 ft of run length
Answer 2: 15A or 20A circuits - 16 AWG up to 100 ft of run length
Answer 3: 20A circuits - 14 AWG and larger
Answer 4: all of these
Answer 4: all of these
240.5(B)(2)(1), (2), and (3)
The standard ampere rating(s) for fuses is(are) _____.
Answer 1: 1A
Answer 2: 6A
Answer 3: 601A
Answer 4: all of these
Answer 4: all of these
240.6(A)
Supplementary overcurrent protective devices are not permitted to be used _____.
Answer 1: to provide additional overcurrent protection for luminaires
Answer 2: to provide additional overcurrent protection for appliances
Answer 3: as the required branch-circuit overcurrent protective device
Answer 4: none of these
Answer 3: as the required branch-circuit overcurrent protective device
240.10
Ground-fault protection of equipment shall be provided for solidly grounded wye electrical systems of more than 150 volts-to-ground but not exceeding 1000V phase-to-phase for each individual device used as a building or structure main disconnecting means rated _____ or more unless specifically exempted.
Answer 1: 1000A
Answer 2: 1500A
Answer 3: 2000A
Answer 4: 2500A
Answer 1: 1000A
240.13
For multiwire branch circuits single-pole breakers with identified handle ties can be used to protect each _____ conductor for line-to-neutral connected loads.
Answer 1: ungrounded
Answer 2: grounded
Answer 3: grounding
Answer 4: neutral
Answer 1: ungrounded
240.15(B)(1)
Feeder taps are permitted to be located at any point on the _____ side of the feeder overcurrent protective device.
Answer 1: load
Answer 2: line
Answer 3: supply
Answer 4: end
Answer 1: load
240.21(B)
Tap conductors not over 25 ft in length are permitted providing the _____.
Answer 1: ampacity of the tap conductors is not less than one-third the rating of the overcurrent device protecting the feeder conductors being tapped
Answer 2: tap conductors terminate in a single circuit breaker or set of fuses that limits the load to the ampacity of the tap conductors
Answer 3: tap conductors are suitably protected from physical damage
Answer 4: all of these
Answer 4: all of these
240.21(B)(2)(1), (2), (3)
The next size up rule in 240.4(B) is not permitted for _____ secondary conductors.
Answer 1: transformer
Answer 2: generator
Answer 3: motor
Answer 4: relay
Answer 1: transformer
240.21(C)
Secondary conductors not over 10 ft long shall be enclosed in a(an) _____.
Answer 1: cable
Answer 2: enclosure
Answer 3: raceway
Answer 4: all of these
Answer 3: raceway
240.21(c)(2)(3)
Outside secondary conductors can be of unlimited length without overcurrent protection at the point they receive their supply if the _____.
Answer 1: conductors are protected from physical damage
Answer 2: conductors terminate at a single overcurrent device equal to or less than their ampacity
Answer 3: overcurrent device is part of the building disconnect
Answer 4: all of these
Answer 4: all of these
240.21(C)(4)(1), (2), and (3)
Circuit breakers and switches containing fuses shall be readily accessible and installed so the center of the grip of the operating handle of the switch or circuit breaker when in its highest position is not more than _____ above the floor or working platform.
Answer 1: 6 ft 4 in.
Answer 2: 6 ft 5 in.
Answer 3: 6 ft 6 in.
Answer 4: 6 ft 7 in.
Answer 4: 6 ft 7 in.
240.24(A)
Overcurrent protective devices shall not be located _____.
Answer 1: where exposed to physical damage
Answer 2: near easily ignitible materials such as in clothes closets
Answer 3: in bathrooms showering facilities or locker rooms with showering facilities
Answer 4: all of these
Answer 4: all of these
240.24(C), (D) and E
_____ shall not be located over the steps of a stairway.
Answer 1: Disconnect switches
Answer 2: Overcurrent protective devices
Answer 3: Knife switches
Answer 4: Transformers
Answer 2: Overcurrent protective devices
240.24(F)