Understanding NEC Articles 215, 220, & 225 Flashcards
Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads the conductor ampacity shall be no less than the noncontinuous load plus _____ of the continuous load.
Answer 1: 80 percent
Answer 2: 100 percent
Answer 3: 125 percent
Answer 4: 150 percent
Answer 3: 125 percent
215.2(A)(1)
Where a portion of a feeder is connected at both its supply and load ends to separately installed pressure connections in accordance with 110.14(C)(2) it shall be permitted to have an allowable ampacity _____ the sum of the continuous load plus the noncontinuous load.
Answer 1: not less than
Answer 2: equal to
Answer 3: not greater than
Answer 4: of 80 percent of
Answer 1: not less than
215.2(A)(1) Ex 2
Feeder grounded conductors not connected to an overcurrent device can be sized at _____ of the continuous and noncontinuous load.
Answer 1: 80 percent
Answer 2: 100 percent
Answer 3: 125 percent
Answer 4: 150 percent
Answer 2: 100 percent
215.2(A)(1) Ex 3
Where a feeder supplies branch circuits in which equipment grounding conductors are required the feeder shall include an _____ to which the equipment grounding conductors of the branch circuits shall be connected.
Answer 1: equipment grounding conductor
Answer 2: grounding conductor
Answer 3: bonding conductor
Answer 4: grounded conductor
Answer 1: equipment grounding conductor
215.6
Where a premises wiring system contains feeders supplied from more than one nominal voltage system each ungrounded conductor of a feeder shall be identified by phase or line and system by _____ or other approved means.
Answer 1: color coding
Answer 2: marking tape
Answer 3: tagging
Answer 4: any of these
Answer 4: any of these
215.12(C)(1)(a)
Where a feeder supplies dwelling units the required SPD shall be a _____.
Answer 1: Type 1
Answer 2: Type 1 or 2
Answer 3: Type 3
Answer 4: any of these
Answer 2: Type 1 or 2
215.18(C)
Where dwelling units are supplied by a feeder and the distribution equipment is ____ the required Type 1 or Type 2 SPD shall be installed.
Answer 1: replaced
Answer 2: repaired
Answer 3: due for maintenance
Answer 4: replaced or repaired
Answer 1: replaced
215.18(D)
Where dwelling units are supplied by a feeder the required SPD shall have a nominal discharge current rating (In) of not less than _____.
Answer 1: 5 kA
Answer 2: 7.50 kA
Answer 3: 10 kA
Answer 4: the available fault current
Answer 3: 10 kA
215.18 (E)
Article _____ provides requirements for calculating branch-circuit feeder and service loads.
Answer 1: 200
Answer 2: 210
Answer 3: 220
Answer 4: 230
Answer 3: 220
220.1
When calculations in Article 220 result in a fraction of an ampere that is less than _____ such fractions can be dropped.
Answer 1: 0.49
Answer 2: 0.5
Answer 3: 0.51
Answer 4: 0.8
Answer 2: 0.5
220.5(B)
Article 215 provides the installation overcurrent protection and conductor sizing requirements for _____ not over 1000V ac 1500V dc nominal.
Answer 1: outside branch circuits
Answer 2: branch circuits
Answer 3: ungrounded conductors
Answer 4: feeders
Answer 4: feeders
215.1
Outlets supplying luminaires shall be calculated based on the maximum _____ rating of the equipment.
Answer 1: power
Answer 2: true power
Answer 3: voltage
Answer 4: volt-ampere
Answer 4: volt-ampere
220.14(D)
Sign and outline lighting outlets are to be calculated at a minimum of _____ for each required branch circuit specified in 600.5(A).
Answer 1: 1000 VA
Answer 2: 1200 VA
Answer 3: 1500 VA
Answer 4: 2000 VA
Answer 2: 1200 VA
220.14(F)
Show window loads shall be calculated at _____ per linear ft of show window.
Answer 1: 90 VA
Answer 2: 120 VA
Answer 3: 200 VA
Answer 4: 240 VA
Answer 3: 200 VA
220.14(G)(2)
Nondwelling unit motors rated less than _____ and connected to a lighting circuit shall be considered general lighting load.
Answer 1: 1⁄16 hp
Answer 2: 1⁄8 hp
Answer 3: 1⁄4 hp
Answer 4: 1⁄3 hp
Answer 2: 1⁄8 hp
220.42(A)
The lighting load unit values of Table 220.42(A) are based on minimum load conditions and _____ power factor and might not provide sufficient capacity for the installation contemplated.
Answer 1: 80 percent
Answer 2: 85 percent
Answer 3: 90 percent
Answer 4: 92 percent
Answer 1: 80 percent
220.42(A) Note
The general lighting load for a school is _____.
Answer 1: 1.50 VA/ft2
Answer 2: 2.50 VA/ft2
Answer 3: 3 VA/ft2
Answer 4: 3.50 VA/ft2
Answer 1: 1.50 VA/ft2
220.42(A) Table
The 125 percent multiplier for a continuous load as specified in 210.20(A) _____ included when using the unit loads in table 220.42(A) for calculating the minimum lighting load for a specified occupancy.
Answer 1: is
Answer 2: is not
Answer 3: is permitted to be
Answer 4: shall not be
Answer 1: is
220.42(A) Table Note
For other than dwelling units or guest rooms of hotels or motels the feeder and service calculation for track lighting shall be calculated at 150 VA for every _____ of lighting track or fraction thereof.
Answer 1: 1 ft
Answer 2: 2 ft
Answer 3: 3 ft
Answer 4: 4 ft
Answer 2: 2 ft
220.46(B)
For dwelling unit load calculations in accordance Article 220 a load of not less than _____ for each 2-wire small-appliance branch circuit shall be applied.
Answer 1: 1000 VA
Answer 2: 1200 VA
Answer 3: 1500 VA
Answer 4: 2000 VA
Answer 3: 1500 VA
220.52(A)
For dwelling unit load calculations in accordance Article 220 a load of not less than _____ for the laundry branch circuit shall be applied.
Answer 1: 1000 VA
Answer 2: 1200 VA
Answer 3: 1500 VA
Answer 4: 2000 VA
Answer 3: 1500 VA
220.52(B)
When sizing a service or feeder for fixed appliances in dwelling units a demand factor of 75 percent of the total nameplate ratings can be applied if there are _____ or more appliances fastened in place.
Answer 1: two
Answer 2: three
Answer 3: four
Answer 4: five
Answer 3: four
220.53
Applying a demand factor of 75 percent to the nameplate rating load of four or more appliances rated 1⁄4 hp or greater or 500 watts or greater that are fastened in place and that are served by the same feeder or service in a one-family two-family or multifamily dwelling shall be permitted. This demand factor shall not apply to _____.
Answer 1: electric vehicle supply equipment
Answer 2: dishwashers
Answer 3: waste disposals
Answer 4: microwave/hoods
Answer 1: electric vehicle supply equipment
220.53(5)
Using the standard load calculation method the feeder demand factor for a duplex containing two 12 kW ranges is _____.
Answer 1: 11 kW
Answer 2: 14 kW
Answer 3: 16 kW
Answer 4: 24 kW
Answer 1: 11 kW
220.55 Table Column C