Understanding NEC Articles 215, 220, & 225 Flashcards

1
Q

Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads the conductor ampacity shall be no less than the noncontinuous load plus _____ of the continuous load.
Answer 1: 80 percent
Answer 2: 100 percent
Answer 3: 125 percent
Answer 4: 150 percent

A

Answer 3: 125 percent

215.2(A)(1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Where a portion of a feeder is connected at both its supply and load ends to separately installed pressure connections in accordance with 110.14(C)(2) it shall be permitted to have an allowable ampacity _____ the sum of the continuous load plus the noncontinuous load.
Answer 1: not less than
Answer 2: equal to
Answer 3: not greater than
Answer 4: of 80 percent of

A

Answer 1: not less than

215.2(A)(1) Ex 2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Feeder grounded conductors not connected to an overcurrent device can be sized at _____ of the continuous and noncontinuous load.
Answer 1: 80 percent
Answer 2: 100 percent
Answer 3: 125 percent
Answer 4: 150 percent

A

Answer 2: 100 percent

215.2(A)(1) Ex 3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Where a feeder supplies branch circuits in which equipment grounding conductors are required the feeder shall include an _____ to which the equipment grounding conductors of the branch circuits shall be connected.
Answer 1: equipment grounding conductor
Answer 2: grounding conductor
Answer 3: bonding conductor
Answer 4: grounded conductor

A

Answer 1: equipment grounding conductor

215.6

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Where a premises wiring system contains feeders supplied from more than one nominal voltage system each ungrounded conductor of a feeder shall be identified by phase or line and system by _____ or other approved means.
Answer 1: color coding
Answer 2: marking tape
Answer 3: tagging
Answer 4: any of these

A

Answer 4: any of these

215.12(C)(1)(a)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where a feeder supplies dwelling units the required SPD shall be a _____.
Answer 1: Type 1
Answer 2: Type 1 or 2
Answer 3: Type 3
Answer 4: any of these

A

Answer 2: Type 1 or 2

215.18(C)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Where dwelling units are supplied by a feeder and the distribution equipment is ____ the required Type 1 or Type 2 SPD shall be installed.
Answer 1: replaced
Answer 2: repaired
Answer 3: due for maintenance
Answer 4: replaced or repaired

A

Answer 1: replaced

215.18(D)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Where dwelling units are supplied by a feeder the required SPD shall have a nominal discharge current rating (In) of not less than _____.
Answer 1: 5 kA
Answer 2: 7.50 kA
Answer 3: 10 kA
Answer 4: the available fault current

A

Answer 3: 10 kA

215.18 (E)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Article _____ provides requirements for calculating branch-circuit feeder and service loads.
Answer 1: 200
Answer 2: 210
Answer 3: 220
Answer 4: 230

A

Answer 3: 220

220.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When calculations in Article 220 result in a fraction of an ampere that is less than _____ such fractions can be dropped.
Answer 1: 0.49
Answer 2: 0.5
Answer 3: 0.51
Answer 4: 0.8

A

Answer 2: 0.5

220.5(B)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Article 215 provides the installation overcurrent protection and conductor sizing requirements for _____ not over 1000V ac 1500V dc nominal.
Answer 1: outside branch circuits
Answer 2: branch circuits
Answer 3: ungrounded conductors
Answer 4: feeders

A

Answer 4: feeders

215.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Outlets supplying luminaires shall be calculated based on the maximum _____ rating of the equipment.
Answer 1: power
Answer 2: true power
Answer 3: voltage
Answer 4: volt-ampere

A

Answer 4: volt-ampere

220.14(D)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Sign and outline lighting outlets are to be calculated at a minimum of _____ for each required branch circuit specified in 600.5(A).
Answer 1: 1000 VA
Answer 2: 1200 VA
Answer 3: 1500 VA
Answer 4: 2000 VA

A

Answer 2: 1200 VA

220.14(F)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Show window loads shall be calculated at _____ per linear ft of show window.
Answer 1: 90 VA
Answer 2: 120 VA
Answer 3: 200 VA
Answer 4: 240 VA

A

Answer 3: 200 VA

220.14(G)(2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Nondwelling unit motors rated less than _____ and connected to a lighting circuit shall be considered general lighting load.
Answer 1: 1⁄16 hp
Answer 2: 1⁄8 hp
Answer 3: 1⁄4 hp
Answer 4: 1⁄3 hp

A

Answer 2: 1⁄8 hp

220.42(A)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The lighting load unit values of Table 220.42(A) are based on minimum load conditions and _____ power factor and might not provide sufficient capacity for the installation contemplated.
Answer 1: 80 percent
Answer 2: 85 percent
Answer 3: 90 percent
Answer 4: 92 percent

A

Answer 1: 80 percent

220.42(A) Note

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

The general lighting load for a school is _____.
Answer 1: 1.50 VA/ft2
Answer 2: 2.50 VA/ft2
Answer 3: 3 VA/ft2
Answer 4: 3.50 VA/ft2

A

Answer 1: 1.50 VA/ft2

220.42(A) Table

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

The 125 percent multiplier for a continuous load as specified in 210.20(A) _____ included when using the unit loads in table 220.42(A) for calculating the minimum lighting load for a specified occupancy.
Answer 1: is
Answer 2: is not
Answer 3: is permitted to be
Answer 4: shall not be

A

Answer 1: is

220.42(A) Table Note

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

For other than dwelling units or guest rooms of hotels or motels the feeder and service calculation for track lighting shall be calculated at 150 VA for every _____ of lighting track or fraction thereof.
Answer 1: 1 ft
Answer 2: 2 ft
Answer 3: 3 ft
Answer 4: 4 ft

A

Answer 2: 2 ft

220.46(B)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

For dwelling unit load calculations in accordance Article 220 a load of not less than _____ for each 2-wire small-appliance branch circuit shall be applied.
Answer 1: 1000 VA
Answer 2: 1200 VA
Answer 3: 1500 VA
Answer 4: 2000 VA

A

Answer 3: 1500 VA

220.52(A)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

For dwelling unit load calculations in accordance Article 220 a load of not less than _____ for the laundry branch circuit shall be applied.
Answer 1: 1000 VA
Answer 2: 1200 VA
Answer 3: 1500 VA
Answer 4: 2000 VA

A

Answer 3: 1500 VA

220.52(B)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

When sizing a service or feeder for fixed appliances in dwelling units a demand factor of 75 percent of the total nameplate ratings can be applied if there are _____ or more appliances fastened in place.
Answer 1: two
Answer 2: three
Answer 3: four
Answer 4: five

A

Answer 3: four

220.53

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Applying a demand factor of 75 percent to the nameplate rating load of four or more appliances rated 1⁄4 hp or greater or 500 watts or greater that are fastened in place and that are served by the same feeder or service in a one-family two-family or multifamily dwelling shall be permitted. This demand factor shall not apply to _____.
Answer 1: electric vehicle supply equipment
Answer 2: dishwashers
Answer 3: waste disposals
Answer 4: microwave/hoods

A

Answer 1: electric vehicle supply equipment

220.53(5)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Using the standard load calculation method the feeder demand factor for a duplex containing two 12 kW ranges is _____.
Answer 1: 11 kW
Answer 2: 14 kW
Answer 3: 16 kW
Answer 4: 24 kW

A

Answer 1: 11 kW

220.55 Table Column C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

For dwelling unit load calculations in accordance Article 220 the branch-circuit load for one wall-mounted oven and one counter-mounted cooking unit shall be the _____ rating of the appliance.
Answer 1: nameplate
Answer 2: ampere
Answer 3: wattage
Answer 4: voltage

A

Answer 1: nameplate

220.55 Table Note 5

26
Q

Table 220.56 may be applied to determine the load for thermostatically controlled or intermittently used _____ and other kitchen equipment in a commercial kitchen.
Answer 1: commercial electric cooking equipment
Answer 2: dishwasher booster heaters
Answer 3: water heaters
Answer 4: all of these

A

Answer 4: all of these

220.56

27
Q

When applying the demand factors of Table 220.56 the feeder or service demand load shall not be less than the sum of the _____.
Answer 1: total number of receptacles at 180 VA per receptacle outlet
Answer 2: VA ratings of all of the small-appliance branch circuits combined
Answer 3: largest two kitchen equipment loads
Answer 4: kitchen heating and air-conditioning loads

A

Answer 3: largest two kitchen equipment loads

220.56

28
Q

The electrical vehicle supply equipment (EVSE) load shall be calculated at the larger of _____ or the nameplate rating of the equipment.
Answer 1: 5000W
Answer 2: 7200W
Answer 3: 10000W
Answer 4: 12500W

A

Answer 2: 7200W

220.57

29
Q

If a motor or air-conditioning load is part of the noncoincident load and is not the largest of the noncoincident loads 125 percent of either the motor load or air-conditioning load whichever is _____ shall be used in the calculation.
Answer 1: less
Answer 2: smaller
Answer 3: larger
Answer 4: less or smaller

A

Answer 3: larger

220.60

30
Q

There shall be no reduction in the size of the neutral or grounded conductor on _____ loads supplied from a 4-wire wye-connected three-phase system.
Answer 1: dwelling unit
Answer 2: hospital
Answer 3: nonlinear
Answer 4: motel

A

Answer 3: nonlinear

220.61(C)(2)

31
Q

Under the optional method for calculating a single-family dwelling unit service general loads beyond the initial 10 kVA are assessed at a _____ demand factor.
Answer 1: 40 percent
Answer 2: 50 percent
Answer 3: 60 percent
Answer 4: 75 percent

A

Answer 1: 40 percent

2020.82(B)

32
Q

A demand factor of _____ applies to a multifamily dwelling with ten units if the optional calculation method is used.
Answer 1: 43 percent
Answer 2: 50 percent
Answer 3: 60 percent
Answer 4: 75 percent

A

Answer 1: 43 percent

220.84(A) Table

33
Q

Where two dwelling units are supplied by a single feeder or service and the calculated load under Part III of this article exceeds that for _____ identical units calculated under 220.84 the lesser of the two loads is permitted to be used.
Answer 1: two
Answer 2: three
Answer 3: four
Answer 4: five

A

Answer 2: three

220.85

34
Q

When calculating a feeder or service load for existing installations if the maximum demand data for a 1-year period is not available the calculated load shall be permitted to be based on the maximum demand (the _____ kilowatts) reached and maintained for a 15-minute interval continuously recorded over a minimum 30-day period.
Answer 1: lowest recorded
Answer 2: highest recorded
Answer 3: lowest average
Answer 4: highest average

A

Answer 4: highest average

220.87(1) Ex

35
Q

In accordance with Article 220 the demand factor for a marina service or feeder with 45 shore power receptacles is _____.
Answer 1: 40 percent
Answer 2: 50 percent
Answer 3: 60 percent
Answer 4: 70 percent

A

Answer 2: 50 percent

220.120

36
Q

Article _____ covers requirements for outside branch circuits and feeders not over 1000V ac or 1500V dc nominal run on or between buildings structures or poles on the premises.
Answer 1: 200
Answer 2: 210
Answer 3: 220
Answer 4: 225

A

Answer 4: 225

225.1

37
Q

In accordance with Article 225 – Outside Branch Circuits and Feeders open individual conductors shall not be smaller than _____ copper for spans up to 50 ft in length and _____ copper for a longer span unless supported by a messenger wire.
Answer 1: 10 AWG 8 AWG
Answer 2: 8 AWG 8 AWG
Answer 3: 6 AWG 8 AWG
Answer 4: 6 AWG 6 AWG

A

Answer 1: 10 AWG 8 AWG

225.6(A)(1)

38
Q

The point of attachment of overhead premises wiring to a building shall in no case be less than _____ above finished grade.
Answer 1: 8 ft
Answer 2: 10 ft
Answer 3: 12 ft
Answer 4: 15 ft

A

Answer 2: 10 ft

225.16(A) and 230.256

39
Q

Where a mast is used for overhead branch-circuit or feeder conductor support it shall have adequate _____ or be supported by braces or guy wires to safely withstand the strain imposed by the conductors.
Answer 1: strength
Answer 2: mobility
Answer 3: length
Answer 4: size

A

Answer 1: strength

225.17(A)

40
Q

Overhead feeder and/or branch-circuit conductors shall not be attached to a mast where the connection is _____ a weatherhead or the end of the conduit and a coupling where the coupling is located above the last point of securement to the building or other structure or where the coupling is located above the building or other structure.
Answer 1: above
Answer 2: below
Answer 3: between
Answer 4: even with

A

Answer 3: between

225.17(B)

41
Q

Overhead feeder conductors shall have a minimum vertical clearance of _____ over residential property and driveways as well as those commercial areas not subject to truck traffic where the voltage does not exceed 300V to ground.
Answer 1: 10 ft
Answer 2: 12 ft
Answer 3: 15 ft
Answer 4: 18 ft

A

Answer 2: 12 ft

225.18(2)

42
Q

If a set of 120/240V overhead feeder conductors terminates at a through-the-roof raceway or approved support with not more than 6 ft of these conductors 4 ft horizontally passing over the roof overhang the minimum clearance above the roof for these conductors shall not be less than _____.
Answer 1: 12 in.
Answer 2: 18 in.
Answer 3: 2 ft
Answer 4: 5 ft

A

Answer 2: 18 in.

225.19(A) Ex 3

43
Q

The requirement for maintaining a 3-ft vertical clearance from the edge of the roof shall not apply to the final feeder conductor span where the conductors are attached to _____.
Answer 1: a building pole
Answer 2: the side of a building
Answer 3: an antenna
Answer 4: the base of a building

A

Answer 2: the side of a building

225.19(A) Ex 4

44
Q

Overhead feeder and branch-circuit clearances from chimneys radio and television antennas tanks and other nonbuilding or nonbridge structures shall not be less than _____.
Answer 1: 3 ft
Answer 2: 6 ft
Answer 3: 8 ft
Answer 4: 10 ft

A

Answer 1: 3 ft

225.19(B)

45
Q

The vertical clearance of final spans of overhead conductors above or within _____ measured horizontally of platforms projections or surfaces that will permit personal contact shall be maintained in accordance with 225.18.
Answer 1: 3 ft
Answer 2: 6 ft
Answer 3: 8 ft
Answer 4: 10 ft

A

Answer 1: 3 ft

225.19(D)(2)

46
Q

Overhead branch-circuit and feeder conductors shall not be installed beneath openings through which materials may be moved such as openings in farm and commercial buildings and shall not be installed where they obstruct _____ these openings.
Answer 1: entrance to
Answer 2: egress from
Answer 3: access to
Answer 4: a safe descent from

A

Answer 1: entrance to

225.19(D)(3)

47
Q

In accordance with Article 225 – Outside Branch Circuits and Feeders raceways on exteriors of buildings or other structures shall be arranged to drain and shall be _____ for use in wet locations.
Answer 1: labeled
Answer 2: listed
Answer 3: approved
Answer 4: listed or approved

A

Answer 4: listed or approved

225.22

48
Q

In accordance with Article 225 – Outside Branch Circuits and Feeders vegetation such as trees shall not be used for support of _____.
Answer 1: overhead conductor spans
Answer 2: surface wiring methods
Answer 3: luminaires
Answer 4: electric equipment

A

Answer 1: overhead conductor spans

225.26

49
Q

Where a raceway enters a(an) _____ from outside it shall be sealed in accordance with 300.5(G) and 300.7(A).
Answer 1: building or structure
Answer 2: crawlspace
Answer 3: highway right-of-way
Answer 4: easement

A

Answer 1: building or structure

225.27

50
Q

Where more than one outside feeder is installed in accordance with 225.30(B) all feeder disconnects in the building shall be _____ in the same location.
Answer 1: grouped
Answer 2: identified
Answer 3: labeled
Answer 4: grouped and labeled

A

Answer 1: grouped

225.30(B)

51
Q

In accordance with Article 225 – Outside Branch Circuits and Feeders the disconnecting means for a building supplied by a feeder shall be installed at a(an) _____ location.
Answer 1: accessible
Answer 2: readily accessible
Answer 3: outdoor
Answer 4: indoor

A

Answer 2: readily accessible

225.31(B)

52
Q

In accordance with Article 225 – Outside Branch Circuits and Feeders there shall be no more than _____ switches or circuit breakers to serve as the disconnecting means for a building supplied by a feeder.
Answer 1: two
Answer 2: four
Answer 3: six
Answer 4: eight

A

Answer 3: six

225.33(A)

53
Q

In accordance with Article 225 – Outside Branch Circuits and Feeders the two to six disconnects for a disconnecting means for a building supplied by a feeder shall be _____.
Answer 1: the same size
Answer 2: grouped
Answer 3: in the same enclosure
Answer 4: of the same manufacturer

A

Answer 2: grouped

225.34(A)

54
Q

Where a building has multiple outside feeders a permanent _____ shall be installed at each outside feeder disconnect location denoting all other services and feeders and the area served by each.
Answer 1: plaque or directory
Answer 2: map
Answer 3: label
Answer 4: guide

A

Answer 1: plaque or directory

225.37

55
Q

In accordance with Article 225 – Outside Branch Circuits and Feeders a building disconnecting means that supplies only limited loads of a single branch circuit shall have a rating of not less than _____.
Answer 1: 15A
Answer 2: 20A
Answer 3: 25A
Answer 4: 30A

A

Answer 1: 15A

225.39A)

56
Q

In accordance with Article 225 – Outside Branch Circuits and Feeders for installations consisting of not more than two 2-wire branch circuits the building disconnecting means shall have a rating of not less than _____.
Answer 1: 15A
Answer 2: 20A
Answer 3: 25A
Answer 4: 30A

A

Answer 4: 30A

225.39(B)

57
Q

For all other installations supplied by a feeder(s) or branch circuit(s) and not specifically identified in 225.39(A) through (C) the feeder or branch-circuit disconnecting means shall have a rating of not less than _____.
Answer 1: 20A
Answer 2: 30A
Answer 3: 40A
Answer 4: 60A

A

Answer 4: 60A

225.39(D)

58
Q

The emergency disconnecting means for one-and two-family dwelling units supplied by an outside feeder shall be installed in a readily accessible outdoor location on or _____.
Answer 1: within sight of the dwelling unit
Answer 2: at the source of power
Answer 3: in the panelboard
Answer 4: closest to the entrance of the feeder cable assembly

A

Answer 1: within sight of the dwelling unit

225.41(A)(1)

59
Q

The emergency disconnecting means for one- and two-family dwelling units supplied by an outside feeder shall have a short-circuit current rating equal to or greater than _____.
Answer 1: 5 kAIC
Answer 2: 10 kAIC
Answer 3: 22 kAIC
Answer 4: the available fault current

A

Answer 4: the available fault current

225.41(A)(2)

60
Q

Where there is more than one emergency disconnecting means for one- and two-family dwelling units supplied by an outside feeder they shall be _____.
Answer 1: separated
Answer 2: adjacent to each other
Answer 3: grouped
Answer 4: away from each other

A

Answer 3: grouped

225.41(A)(3)

61
Q

Where a feeder supplies _____ a surge-protective device (SPD) shall be installed.
Answer 1: dwelling and dormitory units
Answer 2: hotel and motel guest rooms and suites
Answer 3: patient sleeping rooms of nursing homes and limited care facilities
Answer 4: all of these

A

Answer 4: all of these

225.42(A)

62
Q

SPD’s required by 225.42(A) shall be installed _____ the distribution equipment that is connected to the load side of the feeder and contains branch circuit overcurrent protective device(s).
Answer 1: in or adjacent to
Answer 2: within 3 ft of
Answer 3: within 10 ft of
Answer 4: within sight of

A

Answer 1: in or adjacent to

225.42(B)