Turbine building ventilation Flashcards
Explain what the M010 handswitch controls?
M010
Starts C004 fan
Open 133’ F008 damper
Trip exhaust fans C006A/B
Explain what M009 handswitch controls?
M009
Start C004/C005 fans
Open 133’ and 93’ dampers F006/F007
Trip exhaust fans C006A/B
Explain what M011 handswitch controls?
Starts C005 fan
Opens 113’ F009 damper
Trip exhaust fans C006A/B
Explain how the turbine building pressure control system operates
> -.125’ wc F003 (exhaust) opens more. F004 (recirc) closes more.
Less negative….. DP down
< -.125” wc F003 closes more. F004 opens more
More negative….. DP up
What pressure is turbine building maintained at?
Negative (-.125” wc)
What cools 166’ Battery Room fan coil unit
TBCW
What cools all other fan coil units (other than 166’ battery room)
PCW
When does the turbine building exhaust alarm and trips occur in relation to the charcoal filter?
255 deg F charcoal temp high alarm and heater de-energizes
310 deg F charcoal temp HI-HI alarm and exhaust fan trips
When will exhaust fan trip on High inlet temp?
filter train inlet temp 130 deg F exhaust fan trips
What cools the turbine building steam tunnel
PCW