Radwasted Vent Flashcards

1
Q

How does air flow in building? (radioactive areas)

A

flows from low to high potential radioactivity areas

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What will trip exhaust fans?

A

undervoltage (fans must be restarted on loss of power)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What will trip the Hot Lab fan coil unit?

A

135 deg F fan discharge or return air duct

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the power supply for ALL radwaste vent equipment?

A

11DE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Will dampers closing cause a fan to trip?

A

No, but supply fan will trip on low exhaust flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

When is the storage tank vent filter train used?

A

When doing maintenance on the tank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When is the Tunnel Exhaust fan used?

A

when personnel are entering the area, must be operated 30 minutes prior to entry

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What type of pressure is radwaste building maintained at?

A

Negative pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What will trip supply fans?

A

Low flow on exhaust fans

smoke detected in the fan common discharge duct

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How many exhaust fans are required for 2 supply fans

A

1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What cools Hot Lab fan coil unit?

A

PCW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly