How does air flow in building? (radioactive areas)
flows from low to high potential radioactivity areas
What will trip exhaust fans?
undervoltage (fans must be restarted on loss of power)
What will trip the Hot Lab fan coil unit?
135 deg F fan discharge or return air duct
What is the power supply for ALL radwaste vent equipment?
11DE
Will dampers closing cause a fan to trip?
No, but supply fan will trip on low exhaust flow
When is the storage tank vent filter train used?
When doing maintenance on the tank
When is the Tunnel Exhaust fan used?
when personnel are entering the area, must be operated 30 minutes prior to entry
What type of pressure is radwaste building maintained at?
Negative pressure
What will trip supply fans?
Low flow on exhaust fans
smoke detected in the fan common discharge duct
How many exhaust fans are required for 2 supply fans
1
What cools Hot Lab fan coil unit?
PCW