What’s the purpose of the recirc fans?
What ratio is it mixed at?
Mix a quality of air from enclosure building with air from lower regions of the Aux building
> 3:1
What’s the power supplies for the recirc fans?
15BA3
16BB3
How do dampers respond after initiation?
F021/F022 are open on initiation and remain open ( Enclosure bldg to recirc fans)
At -.20” wc is reached, aux steam tunnel F005/F006 go to intermediate
90 seconds later all other dampers go to intermediate
If enclosure building >.20”wc, dampers re-open
What will trip the heater in SBGT?
> 200 deg F (auto reset)
> 225 deg F (manual reset)
What setpoints will start the standby, SBGT?
< 8500 scfm running enclosure building recirc fan low flow
<1250 scfm running exhaust filter train low flow
> .20” wc in enclosure building low negative pressure
How do you place a train of STBY gas in standby?
IF:
> 8500 scfm running enclosure bldg recirc fan
> 1250 scfm running exhaust filter train flow
> .20” w.c. in enclosure bldg pressure
THEN: Mode switch to STBY amber light reset manual initiation logic stop SBGT train
How do the exhaust fan vanes react off initiation? (F500A/B)
Initially open for 120 seconds or .75” w.c. enclosure bldg pressure.
THEN:
Modulate to maintain 3875 scfm system flow rate through the filter train
what signals start standby gas?
- 41.6” Rx water level
1. 23 psig drywell pressure
30 mr/hr fuel pool sweep
3.6 mr/hr FHA exhaust
purpose of demister?
removes water
purpose of electric heater?
reduces humidity to 70%
purpose of prefilter?
removes large particle matter
purpose of HEPA (1st filter)
Removes fine particulate matter
purpose of charcoal filter?
removes gaseous IODINE
purpose of 2nd HEPA filter?
Collects carbon fines exhaust from charcoal beds
Will stop handswitch secure STBY gas with signal sealed in?
NO