Aux vent Flashcards

1
Q

What will trip a running fan coil unit?

A

Either secondary CTMT isolation valve F006, F007 not full open

Smoke detector or high temp actuation

low inlet temp < 35 deg F for freeze protection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

which zones will trip if F006 or F007 are not full open?

A

Zones 1,2,3,4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What will start the standby fans for the Aux steam tunnel?

A

Low DP sensed on running fan or high steam tunnel temp

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

what must be done to ensure STBY fan does not auto start?

A

Open the breaker

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

what happens on an actuation of a smoke detector?

how is it reset?

A

Fan trips

reset locally then handswitch taken to stop and back to start

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What cools ESF switchgear rooms

A

PSW or SSW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What cools ECCS pump rooms?

A

SSW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What cools Aux steam tunnel?

A

PCW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How does the F006 and F007 fail?

A

closed on loss of power or air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly