SPMU Flashcards
What’s the range for narrow range?
18’ - 19’
What’s the range for wide range?
10.5’ - 25.5’
What’s the range for accident range?
25’ - 35’ it indicates the status of CTMT water overflowing the weir wall and into the drywell to enter RPV through the break
60’ - 75’ water adequate to cover the top of active fuel. CTMT pressure is lost @ 75’ due to highest tap being covered
How much water will SPMU dump into the supp pool?
270,000 gallons
Why is the volume limited to the separator pool?
So if dump occurs in Refuel bundle at highest point on grapple, approximately 1 foot of water would still cover the bundle
When do we disable SPMU?
In refuel
Will placing handswitch in TEST after a little LOCA stop the 29 minute timer?
NO
How can SPMU be manually initiated?
Mode switch in Auto
SPMU switch in TEST
Both SPMU manual initiation pushbuttons pressed
what’s the purpose of SPMU?
Provides sufficient water to the suppression pool to keep drywell vents covered during and after a LOCA
where does suppression pool make-up water come from?
separator pool
when are the valves for SPMU located?
161’ CTMT 180 degrees apart
what are the setpoints for a large LOCA?
- 150.3” rx water level OR
1. 39 psig DW pressure OR
LPCI/LPCS manual initiation AND
Low-low suppression pool level 17.5’ or both SPMU manual initiation pushbuttons
What are the setpoints for a small LOCA?
- 41.6” Rx water level OR
1. 23 psig DW pressure OR
NSSSS manual initiation AND
29 minute timer