Splicing Flashcards
An ideal cable joint (splice) should be as strong and reliable, both ? , as the cable in which it is installed.
electrically and physically
There are ? factors that cause longitudinal stresses in a splice.
3
Of the factors that cause longitudinal stresses in a splice, using unlike splicing materials is not one of them.
False
The way the different parts fit together in relation to each other (geometry) in a joint is one of the factors that cause longitudinal stresses in a splice.
True
The ? is another factor that causes longitudinal stresses in a splice
Connector shape
A great deal of emphasis is placed on the elimination of air voids in a joint (splice) because they may be potential sources of ? .
Corona
When the stress in the air voids in a joint exceeds the breakdown value it ?
Ionizes
Produces ozone
Becomes conductive
The product that first allowed medium and high voltage splices to be connected using standard crimp-type (compression) connectors is ? .
Semi-conducting tape
The yellow (color coded) mastic material refers to the ? .
Stress relief mastic
A ? can be defined as two or more conductors joined with a suitable connector, re-insulated, re-shielded, and re-jacketed with compatible materials applied to a properly prepared surface.
Splice
There are ? reasons for splicing shielded cables.
5
Tapping into an existing cable is one of the reasons for splicing shielded cables.
True
The industry standard that establishes electrical ratings and test requirements of shielded cable splices (joints) is the IEEE Standard ? ,
404
A hand-wrapped tape splice is no longer one of the common types of splices used because it is too difficult to apply.
False
One of the common types of splices used is the ? elbow splice.
600 amp
There are two shrink splices in common use
Heat shrink
Cold Shrink
One function of a medium or high voltage splice is to maintain metallic shield continuity.
True
Controlling ? in the connector area is a function of a medium or high voltage splice.
Electrical stress
A function of a medium or high voltage splice is to provide for ? of service life.
30-40+
There are ? basic steps in building a splice.
5
The proper type of connector for joining the aluminum conductors of two 15-kilovolt shielded cables is a(n) ? connector.
aluminum (AL/CU) inline compression
Modern manufactured splice kits are normally easier and faster to install than traditional splices. However, they are generally more sensitive to ?
Proper Kit Selection
Cable preparation dimensions
Unique installation steps
There is/are ? layer(s) of shielding that must be replaced when constructing a medium or high voltage splice.
3
The functions that a splice jacket perform include are
Mechanical protection
Moisture sealing