Who can perform the routine in-service inspections?
Anyone knowledgeable of the operations, the tank, and product stored in the tank
API 653 par 6.3.1.1
What membrane stress is that is required to cause a brittle fracture?
7 ksi (7000 PSI)
API 653 par 5.3.7
How often must the routine-in-service inspection by performed?
At least MONTHLY
API 653 par 6.3.1.2
Who is required to perform external inspections?
Authorized Inspector
API 653 par 6.3.2.1
What is the required inspection internal for an external inspection?
Lesser of 5 years or RCA/4N
API 653 par 6.3.2.1
Who determines the extent of thickness measurements?
Owner/Operator
API 653 par 6.3.3.1
What is the maximum internal for taking thickness measurements, when the corrosion-rate is not known?
5 years
API 653 par 6.3.3.2a
What is the required internal for taking thickness measurements, when the corrosion-rate is known?
Lesser of 15 years or RCA/2N years
API 653 par 6.3.3.2b
When is it acceptable to not take thickness measurements?
If the Internal Interval is shorter than the thickness monitoring internal
API 653 par 6.3.3.3
Surveys of the cathodic protection system is performed in accordance with what code?
API 651
API 653 par 6.3.4.1
What is the required internal for performing cathodic protection surveys?
Annual
API 653 par 6.3.4.1 & API 651 par 11.3.1.2
How often must the sources of impressed current be checked on a cathodic protection system?
At least every two months
API 653 6.3.4.1 & API 651 par 11.3.2.2
Who must conduct the internal inspection and supervise the collection of data?
Authorized inspector
API 653 par 6.4.1.2
When can an on-stream inspection be perofrmed in lieu of visual internal inspection of the tank?
When the inspection is being performed to determine the condition of the tank bottom
API 653 par 6.4.1.2
By what date must the tank owner/operators have to be in compliance with API 653
January 2017
API 653 par 6.4.2