API 575 Flashcards
Inspection Practices for Atmospheric and Low-pressure Storage Tanks
What is the maximum internal pressure for tanks per API 650 & API 653?
2.5 psig
API 575 par 3.3
What is the exterior surface of the tank bottom called?
Bottom slide
API 575 par 3.6
What is a device that protects atmospheric storage tanks by maintaining the pressure difference between the tank vapor space and the out atmosphere to just a few ounces per in²?
Pressure-Vacuum Vent
API 575 par 4.2.2
What is the most common type of AST?
Fixed Cone Tank
API 575 par 4.2.3
What is the purpose of a geodesic dome on a tank?
Prevent vapor loss and to eliminate the need for water draw off
API 575 4.2.3
What is the maximum internal pressure for tank per API 620?
15 psig
API 4.3.2
What are atmospheric storage tanks generally inspected?
To determind the physical condition of the tank and to determine the type, rate, and causes of damage mechanisms and associated deterioration
API 575 5.1
What is the primary cause of deterioration of steel storage tanks?
Corrosion
API 575 5.2
During the inspection of a tank, a section of the bottom is removed. Several globs of clay are found in the pad. What would you suspect?
Pitting corrosion on bottom side of tank bottom
API 575 5.2.1 Note: API 652 5.4 indicates ‘severe’ corrosion can be caused
What usually causes internal corrosion of an atmospheric storage tank in vapor zone?
H2S vapors, H2O, O2 or combination
API 575 5.2.2
Where is the most likely point and one of the potentially most critical points for a crack to occur in a large storage tank?
Shell-to-bottom weld
API 575 5.4
How should AST foundations be checked for settlement?
Surveyor’s level
API 575 8.2.3
Coatings (paint, etc) may affect UT readings. What should be done?
Compensate for the coating
API 575 8.2.8.2
A riveted of bolted tank should have a number of random selected rivets or bolts checked for tightness. How is this done?
Tapping rivet or bolt head laterally with hammer while holding the other side
API 575 8.2.8.7