SBC Eductor Chart Flashcards
What kind of nozzles should be chosen for using foam?
Selectable gallonage nozzles
How do you reset foam pro stats
Hold up & down to Clear memory
E 9213
A 9153
T 1214
ELKHART - 95GPM 200PSI 100’ 300’
ANGUS - 95GPM 150PSI 150’ 300’
TFT - 125GPM 200PSI 100’ 400’
GPM flow for Elkhart eductor?
95GPM
What happens when foam tank becomes empty
It will only run for 2 minutes
“LoCon” will blink
After 2 minutes “No Con” will display and pump will go to standby
What are the sizes of the Angus eductor inlets &outlets
1.5” inlet & outlets
Reducer needed
What is the minimum hose length for the TFT foam eductor?
100’
What is the required inlet pressure for the TFT foam eductor
200psi
What are the sizes of the inlet & outlet of the Elkhart eductor?
Inlet (2.5”)
Outlet: 1.5”
Minimum hose length when using Elkhart eductor
100’
Freeway line
What class of foam would you use the Elkhart eductor?
Class B foam
What is the maximum hose length allowed for the TFT eductor?
400’
What pressure should one use if supplying foam via the blitz line to the Elkhart foam eductor?
206psi
6psi FL using blitz line
Inlet Pressure for Elkhart eductor
200psi
What is the minimum hose length needed for Angus eductor?
150’