If a gas shut-off valve complies with
_______ it is
permitted without requiring a 5G label on
5-psig pressure gas lines.
ASME B16.33
A piping joint should be suitable for the
_________ conditions,
and must be chosen with consideration to mechanical strength and tightness of joint under service conditions.
Pressure, temperature
In administration, when
______
alternative materials or methods not
specifically prescribed by the IFGC may be permitted.
designed
by a registered design professional
A category IV
condensing appliance shall be provided with an/a __________
where damage to any building part occurs as the result of
condensate drainage stoppage.
Auxiliary drain pan
Where must a gas shut-off valve for an appliance be installed?
upstream of a union
Regarding structural safety, truss components and members may not be cut, drilled, notched, spliced or otherwise altered in any way unless a ________ gives written approval and agreement.
registered design professional
For installation of appliances in an enclosed parking garage, what standard applies?
NFPA 88A
An appliance, equipment, and/or system installation for a structure in a ________ must be at or above the required elevation for utilities and attendant equipment, as detailed in the International Building Code Section 1612.
flood hazard area
The maximum infiltration rate to be used in equations for indoor combustion air when the air-infiltration-rate is known is ________ ACH.
0.60
In general regulations, appliances not listed:
may be allowed, depending on an engineering evaluation
Regarding combustion air, ________ must be provided when the operation of appliances is interfered with by clothes dryers, exhaust fans, and kitchen ventilation systems.
Makeup air
When installed in a private garage, appliances must be ________ feet or more above the floor.
6
Regarding general regulations, when a single wall-mounted unvented room heater is installed in a bedroom, it is limited to an input rating of not more than:
10,000 BTU/Hr
Who is a code official authorized to accept inspection reports from?
approved agencies or individuals
Used fittings, pipe, valves and other materials must be free of ________ to be used in a gas piping system.
foreign materials
In combustion air, each opening of a horizontal duct that communicates with the outdoors must have at least 1 square inch per ________ BTU per hour of total input rating of all appliances in the enclosure for free area.
2,000
Gas shut-off valves for appliances must be ______ from the appliance or less.
6
Regarding general regulations, at the time of inspection, ________ instructions from the manufacturer must be available on the job site.
Installation
Threaded fittings for steel gas piping must be ______ inches or less unless specifically approved.
4
For gas piping outlets, the unthreaded part must extend beyond finished ceilings and walls at least ______ inch(es).
1”
The ________ for multiple meters must mark each meter’s piping system with permanent identification that has been approved.
Installer
An appliance must be in a location to allow proper ________ of combustion, ventilation and dilution air.
Circulation
For access, rooms containing appliances that are not in a dwelling unit must have a door and a passageway with an unobstructed clearance of 80 inches high and ________ inches wide or more.
36”
Attics with appliances installed must have a level space for service at least ________ inches deep by ________ inches wide.
30, 30
Of the following, which pipe assembly type is only allowed in installations outside of buildings or within hydrogen cutoff rooms?
flange connections
When an appliance shut off valve is at a manifold, it does not need to be:
in the same room as the appliance
A door, drapery, or other such object must never be closer than ______ inches to any part of the register of a floor furnace.
12”
A shut-off valve for gas service must be within 6 feet (1829 mm) of the appliance, but must also be within the same:
Room
There must be markings on hydrogen piping systems each time there is a:
wall penetration
In structural safety, the minimum required space in a cut, notched or bored nonstructural cold-formed steel wall stud with at least two openings is_________.
24 inches
For Group H occupancies or control areas where open dispensing, handling or use of combustible, explosive or flammable materials occurs, equipment and appliances with an ignition source______________.
must be elevated
In installation, a concrete slab supporting an appliance must be ________ inches or more above the adjoining grade.
3
A clearance of ________ inches or more is required in front of an appliance, when outdoor combustion air is provided through a single opening.
6
In gas piping installation, the calculations for the volumetric flow rate of gas to be provided in cubic feet per hour must use the ________, adjusted for altitude, of the appliances.
maximum input
When replacement or repair of defective materials or parts is necessary, it must be in a manner to preserve the original ________ or approval.
Listing
Installation of CSST piping systems must be compliant with the listing conditions, manufacturer’s instructions, the ________, and this code.
terms of their approval
Installation of CSST piping systems must be compliant with the listing conditions, manufacturer’s instructions, the ________, and this code.
terms of their approval
Regarding gaseous hydrogen systems, in areas other than ___________________, threaded and flanged connecti
hydrogen cutoff rooms and outdoors
When an opening obtains indoor combustion air from a different story, it requires a total of at least ________ square inch(es) of free area per 1,000 BTU/h of the total input rating of appliances.
2
When an opening obtains indoor combustion air from a different story, it requires a total of at least ________ square inch(es) of free area per 1,000 BTU/h of the total input rating of appliances.
2
Supports for 1/2-inch copper tubing gas piping must be ______ feet apart or less.
4