Chapter 3 - General Regulations Flashcards
Appliances, equipment, and systems regulated by this code shall not be located in an:
Elevator shaft
Notching at the end of joists shall not exceeded _____.
1/4 of the joist depth
Holes bored in joists shall not be within ______ of the top and bottom of the joist.
2 inches
The diameter of holes bored through joists shall not exceeded______ of the depth of the member
1/3
Notches in the top or bottom of the joist shall not exceed ______ Of the joist depth
1/6
Notches shall not be located in the middle ______ of the span
1/3
In exterior walls and bearing partitions, any wood stud is permitted to be cut or notched to a depth, not exceeding
25% of its width
Cutting or notching studs to a depth, not greater than ________ of the width of the stud is permitted in non-loadbearing partitions supporting no loads other than the weight of the partition.
40%
The diameter of bored holes in wood studs shall not exceed _____ of the stud depth
40%
The diameter of bored holes in wood studs shall not exceed ______ of the stud depth where each stud is doubled
60%
The edge of the bored hole shall not be closer than ______ to the edge of the stud
5/8 inch
Bored holes shall not be located at the same section of stud as a:
Cut or notch
True or false appliances shall not be located in storage closets
True
True or false appliances are allowed to be located inside of bathrooms
False
True or false direct vent appliances are allowed in sleeping rooms, bathrooms, toilet rooms, storage, closets, or surgical rooms
True
The minimum required volume shall be ______ cubic feet per 1000 BTU of appliance input rating for combustion air
50 ft.³
For indoor combustion air where combining spaces on the same story, each opening shall have a minimum free area of:
One inch per 1000 BTU of the total input rating of all appliances in the space
The minimum opening shall be no less than:
100 in.²