Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than ______ above the lowest portion of the interior of the chimney flue.

A

12”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Masonry chimney flues shall be provided with a cleanout opening having a minimum height of:

A

6 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The upper edge of the opening shall be located not less than _____ below the lowest chimney inlet opening.

A

6 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Venting system shall not extend into or pass through any

A

Fabricated, air duct or furnace Plenum

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Chimneys shall extend _____ above the highest connected appliance, draft hood, or flue collar

A

5 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The locations of gas vents shall comply with table?

A

503.6.5

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Single wall metal pipe shall be constructed of galvanized sheet steel, not less than

A

0.0304 inches thick

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Single wall metal pipe shall not originate in any unoccupied attic or concealed space and shall not pass through

A

Any attic, inside wall, concealed space or floor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where the vent connector used for an appliance having a draft hood or a category, one appliances located in or passes through attics, crawlspaces, or other unconditioned spaces that portion of the vent connector shall be listed as

A

Type B or type L

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

A vent connector shall be installed without drips or sags and shall slope upward toward the vent or chimney, not less than

A

1/4 inch per foot

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The maximum horizontal length of a single wall connector shall be ____ of the height of the chimney or vent

A

75%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The maximum horizontal length of a type B double wall connector shall be ______ the height of the chimney or vent

A

100%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How far above the bottom of the wall furnace, in vertical feet, must a Type B-W gas vent terminate?

A

12 feet

503.6.6 Minimum height

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Where steel shield plates are required to protect vents in a concealed location from physical damage, what is the minimum required thickness?

A

No. 16 gauge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

How many feet must single-wall metal pipe terminate vertically above the highest draft hood outlet for an appliance?

A

5 feet

503.7.3 Termination

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

For cleaning, inspection, and replacement, a vent connector must be provided with ________ for its entire length.

A

Ready access

503.10.12 Inspection

17
Q

If a gas vent terminates 8 feet or less from a vertical wall, the termination must be at least ________ feet above any part of a building that is 10 feet or less from it.

A

2 feet

503.6.5 Gas vent terminations

18
Q

A noncombustible, nonventilating thimble is required when a single-wall metal pipe passes through a roof made of combustible material, extending at least 6 inches below the roof, and a minimum of ________ inches above.

A

18

503.7.5 Roof penetrations.