Chapter 6 - specific appliances Flashcards
The design of the installation shall include adequate provision to permit, direct fired industrial air heaters to operate at rated capacity by taking into account the structures, design, infiltration rate, providing properly design, relief openings, or an interlock power exhaust system or a:
or a combination of these methods
Dryer exhaust systems shall be _____ of all other systems, and shall convey the moisture, and any products of combustion to the outside of the building.
Independent
Ducts that exhaust clothes dryers shall not penetrate or be located within any fire blocking, draft stopping or any wall, flooring or ceiling or other assembly required by the international building code unless duct is constructed of
Galvanized steel, or aluminum
Dryer installations exhausting more than ____ a minute shall be provided with make up air.
200 ft.³
Where a closet is designed for the installation of a clothes, dryer, an opening having an area of not less than ________ shall be provided in the closet enclosure, or make up air shall be provided by other approve means
100 in.²
Dryer duct shall be a minimum of what size
4 inches
Dryer ducts shall have a smooth interior finish and shall be constructed of metal not less than:
0.016 inches thick
Transition ducts shall not be more than_____ long
8 feet
The maximum length of the dryer exhaust duct shall be:
35 feet
Where the dryer exhaust duct equivalent length exceeds 35 feet, the equivalent length of the exhaust duct shall be identified on a permanent label or tag located within _____ of the exhaust duct
6 feet
Sauna heater shall be equipped with a thermostat that will limit room temperature to:
194°F
If the thermostat is not an integral part of the sauna heater, the heat sensing element shall be located within
6 inches of the ceiling
The letters indicating the harmful effects of the sauna for any persons and pour house shall be how tall
Not less than 1/4 inch
Outdoor air inlets for residential portions of a building shall be covered with a screen, having what size openings?
1/4 inch
Suspended type unit heaters shall be installed with clearances to combustible materials not less than_____ on the sides
18 inches