Purple K Dry Chem Extinguisher Flashcards
When will we use Purple K dry chem extinguisher for what type of fires?
1
METHANOL fires
Also effective on Gas, Diesel, and Compressed gas fires
MDG-CG
Mike Daly gets completely gassed.
Purple K has demonstrated a SUPERIOR extinguishing capability in —- fires.
1
Methanol
When using Purple K Dry Chem extinguisher, direct stream at?
2.3.3
Base of flames a side to side motion.
LPG fires, when do you extinguish them?
4.9
Once fuel source is able to be shut off.
LPG vapors are heavier than air.
LPG Fires
T/F
Adjust fog position 1st then open for water.
4.9
False
Open then Adjust to the FOG position
Purple K Dry Chem extinguisher.
Discharge range?
Discharge time?
Coverage?
2.2
Range is 19 to 20 feet
Discharge time 11 seconds
Coverage approximately 30 ft.²
Purple K Dry Chem extinguisher shall be checked when?
2.4
Each tour.
Thoroughly examined once a month.
Flammable liquid spill fire.
1-Approach from —-.
2-Nozzle at —- angle.
3-Stop walking at a point approximately — to — from the front edge of the fire.
4.1
1- Upwind
2- 45 degree
3- 10-12 feet from edge
Flammable liquid spill fire.
Direct the stream — inches/feet ahead of flame edge.
What type of motion?
4.1
6 inches ahead of flame edge
RAPID side to side motion
T/F
Flammable liquid spill fire.
With the Dry Chem extinguisher it is usually 6 inches.
Except flammable liquid pressure fire, which is 15 feet from leading edge.
Spill - 6 inches
Pressure- 15 feet