Pre Test Review Flashcards
What are the at power trips blocked by P7?
PRZ Pressure Low
PRZ Water Level High
RCS Loss of Flow
UV on RCP Busses
UF on RCP Busses
RCP Breaker Position
What are the inputs to OT Delta T?
Delta T
Tave
AFD
PRZ Press
What does OT Delta T Protect from?
DNB
What are the inputs for OP Delta T?
Delta T
Tave
What does OP Delta T protect from?
KW / Ft
What starts the CEQ Fans?
1 psi in Containment.
NOT Phase A
What is the function of P4?
+ Low Tavg = FWI
Permits manual block of auto SI Signals
What are the setpoints for P6 while going up in power?
10-10 Amps
What are the setpoints for P6 coming down in power?
6 x 10-11 amps
When does the SR Hi flux at SD alarm blocked clear?
10-10 amps
P6
What are the 4 functions of P10?
Permits manual block of:
- PR Hi Flux Trip, Low Setpoint
- IR Trip
- IR Rod Stop
Also is the backup de-energization of SR
Which rod stops are for auto and manual rod withdrawal?
C1
C2
C3
C4
How are rods affected during a PR NI failure - High?
Rods insert and will not withdraw bc of C2
What is C9?
1 Circ Pump Breaker Closed
CRID II
3/3 Condenser Vac >= 20.6 “Hg
When is AMSAC enabled?
2/2 Turbine Impulse Pressures >40%
When is the runback of the MFP enabled?
> 60% power ish. Actually based on the auto dp setpoint for mfps
What is the only pressurizer level failure that will not cause a trip with no operator action?
Bistable fails high
While PRZ Heaters be protected during a cooldown?
No. Actual level will be less than 17% when indicated on the hot cal
What is the TRM Temperature for aux spray delta T?
320*F
Which pressure channel inputs into QMO-225, East CCP ELO?
NPP-151
Which pressure channel inputs into QMO-226, West CCP ELO?
NPP-153
What must be done if SDM is not within the COLR limits?
Borate to restore within 15 mins
What is QLC-451, VCT Level control primarily responsible for?
Makeup
Starts at 14%. Stops at 24%
Divert trips open at 87%
Has high, Low and Low low alarm. As well as MU Not in Auto
What is QLC-452, VCT Level control primarily responsible for?
Divert
Starts at 78%. Full open at 87%.
Has Low and Low Low alarm
The turbine trip controller maintains temperature at ______ using a maximum of _____ groups of valves.
547*F
2 Groups
How many groups of valves are available for a load rejection?
2 groups for C7A
3 groups for C7B
How do you know how many groups of valves are open on a turbine trip?
Temperature.
10*F differential = 1 group trips open
20*F differential = 2nd group trips open
How many groups are available in steam pressure mode below 541*F?
1 group after going to bypass
What is the ECCS Acceptance Criteria?
Peak Clad Temp < 2200*F
Max Clad Oxidation < 17%
H2 generation < 1% max
Coolable geometry
What are the typical injection pressures and flows for the ECCS Pumps?
CCP 2300# 150-550 gpm
SI 1600# 400-600 gpm
RHR 200# 4500 gpm
What are the tech specs for the accumulators?
Volume 921 - 971 cu ft
Pressure 585 - 658 psig
Boron 2400-2600 ppm
What is QPTR?
Max of all Upper (lower) vs Average of all Upper (lower)
What must be done if AFD is not in target band at > 90% power?
15 mins to restore or get below 90% in another 15 mins
What must be done if you’re between 50-90% power and AFD is not in the target band?
Reduce to < 50% power in less than 30 mins