After Thoughts Flashcards
What is the interlock with both CCP breakers open?
LD Orifice Valves will close
QRV-160, 161, and 162
What will close the LD Orifice Valves? (4 things)
Phase A
When either LD Isolation Valve is closed
Loss of both CCPs
PRZ Level at 17%
What is the interlock to open the LD Isolation Valves?
Will not open if any orifice isolation valve is open
What is the interlock with IMO-128?
NPS-122, Loop 1, Ch 3
What is the interlock with ICM-129?
NPS-121, Loop 2, Ch2
After swap to CL Recirc, how long do you have to isolated the SAT?
5 minutes to keep the NAOH from messing up the pH
How do you adjust the temperature for the H2 Recombiners?
Adjust the KW
What is the MFP low condenser vacuum trip?
U1 = 20” Hg
U2 = 20.3” Hg
What is the MFP Low Lube Oil pressure trip?
4# with a 5 second time delay
What is the Low Suction pressure MFP Trip?
180# with a 5 sec time delay
What is the Low Pressure auto start for CCW?
80#
What is the low pressure auto start for ESW?
40#
What is the Low Pressure auto start for NESW?
U1 = 55#
U2 = 60#
What are the design features to prevent SFP from draining?
No Gravity Drains
Suction’s 19.5” below surface
Return Lines > 6’ above fuel
Anti-Siphone Holes 4” below surface
Skimmer 6” below normal surface
What is the low pressure autostart for the CBP?
325#
What is the low pressure auto start for the hotwell pumps?
130# for unit 1
110# for unit 2
RCDT Inputs?
Accumulator Drains
RCS Loop Drains
Regen and XS LD HX Drains
RX Vessel Flange Leakoff
Refueling cavity
What is the U1 Turbine Low Vac Trip from DCS?
22.5” Hg at 100% power
What is the U1 Turbine Trip from Low Oil Pressure?
8 psig for > 5 secs
What is the U2 Turbine Trip from Low Vacuum?
22.5” Hg at 100% power